Honeywell 8000 Thermostat User Manual


 
62-0266—01 6
0320 Temperature
Indication
Scale
0 0—° F
1—° C
0330 Daylight
Saving
2 0—Disabled
1—Enabled (US 1987)
2—Enable (US 2007)
3—Enabled (Europe)
0340 Remote
Temperature
Sensor
0 0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor
Averaging would
not include on-
board sensor. It is
accomplished by
series/parallel
combinations.
2 applies only to
Heat Pump
applications
(allowing
compressor lockout
while displaying
temperature).
0350 Heat Pump
Compressor
Lockout
0 0—None
15(-9.5)—15° F (-9.5° C)
20(-6.5)—20° F (-6.5° C)
25(-4.0)—25° F (-4.0° C)
30(-1.0)—30° F (-1.0° C)
35(1.5)—35° F (1.5° C)
40(4.5)—40° F (4.5° C)
45(7.0)—45° F (7.0° C)
Only shown for
heat pump systems
with more heat
stages than cool
selected and
remote sensor
selection is outdoor
for control.
Must enforce a
dead band
between this and
Auxiliary Lockout
0360 Heat Pump
Auxiliary
Lockout
0 0—None
40(4.5)—40° F (4.5° C)
45(7.0)—45° F (7.0° C)
50(10.0)—50° F (10.0° C)
55(13.0)—55° F (13.0° C)
60(15.5)—60° F (15.5° C)
Only shown for
heat pump systems
with more heat
stages than cool
selected and
remote sensor
selection is outdoor
for control.
Must enforce a
dead band
between this and
Heat Pump
Compressor
Lockout.
Table 1. Installer Setup (Continued).
Installer
Setup
Number
Installer
Setup
Name
Default
Setting All Settings Notes