Heatmaster 200 F Boiler User Manual


 
6
TECHNICAL SPECIFICATION
MAXIMUM OPERATING CONDITIONS
Maximum service pressure
(tank full of water)
- Primary circuit: 3 bar
- Secondary circuit: 10 bar
Test pressure
(tank full of water)
- Primary circuit: 4.5 bar
- Secondary circuit: 13 bar
Operating temperature
- Maximum temperature: 90°C
Water quality
• Chlorures: < 150 mg/l (304)
< 2000 mg/l (Duplex)
• 6 ph 8
BURNER CHAMBER PLATE
The burner chamber plate secures the burner with 4 screw threads
(M 8). It is thermally insulated to protect it from the heat.
HM 200 N HM 200 F
Peak delivery at 40°C L/10’ 1570 1675
Peak delivery at 45°C L/10’ 1350 1444
Peak delivery at 60°C L/10’ 915 961
Peak delivery at 70°C L/10’ 737 755
Peak delivery at 80°C L/10’ 586 586
Peak delivery at 40°C L/60’ 4920 5976
Peak delivery at 45°C L/60’ 4221 5131
Peak delivery at 60°C L/60’ 2925 3126
Peak delivery at 70°C L/60’ 2412 2309
Peak delivery at 80°C L/60’ 1712 1712
Continuous delivery at 40°C L/h 4020 5161
Continuous delivery at 45°C L/h’ 3446 4424
Continuous delivery at 60°C L/h’ 2412 2598
Continuous delivery at 70°C L/h’ 2010 1864
Continuous delivery at 80°C L/h’ 1352 1352
N.B.:
The outputs above are given for a hot water temperature of 90°C and a cold water temperature of 10°C.
DOMESTIC HOT WATER PERFORMANCES
45°
Ø
130
Ø
1
70
Ø 22
Ø 4
6
4 x M8