Heatiator HEIR36H Indoor Fireplace User Manual


 
41
Heatilator •
HEIR36, HEIR42, HEIR50 • 2285-900 Rev. D • 8/12
120º
Figure 10.5 Securing Vertical Pipe Sections
120º
Figure 10.6 Securing Horizontal Pipe Sections
C. Disassemble Vent Sections
Rotate either section (see Figure 10.7) so the seams on
both pipe sections are aligned as shown in Figure 10.8.
• Pull carefully to separate the pieces of pipe.
B. Secure the Vent Sections
• Vertical runs of DVP pipe must be supported every 8 ft.
(2.44 m) after the 25 ft. (7.62 m) maximum unsupported
rise.
• Horizontal sections must be supported every 5 feet
(1.52 m).
• Vent supports or plumbers strap (spaced 120º apart)
may be used to support vent sections. See Figures 10.5
and 10.6.
• Wall shield restops may be used to provide horizontal
support to vent sections.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate.
Use vent run supports and connect vent sections per in-
stallation instructions. DO NOT allow vent to sag below
connection point to appliance.
Figure 10.8 Align and Disassemble Vent Sections
Figure 10.7 Rotate Seams for Disassembly