A. Chimney Requirements
Measure vertical distances from the base of the replace
as shown in Figure 8.2.
20 ft (6.10 m) max.
pipe between an
offset & return
Ceiling firestop
35 ft (10.7 m)
max. straight
unsupported
chimney height
14 ft (4.27 m) min. height
(no offset-return)
50 ft (15.24 m) max. height
6 ft (1.83 m) max.
unsupported chimney
above roof
38 1/2 in. (978 mm)
Effective Height
Figure 8.2 Chimney Requirements
Table 8.1
Minimum overall straight height 14 ft (4.27 m)
Minimum height with offset/return 14.5 ft (4.42 m)
Maximum height 50 ft (15.24 m)
Maximum chimney length between an offset
and return
20 ft (6.1 m)
Maximum distance between chimney
stabilizers
35 ft (10.67 m)
Double offset/return minimum height 20 ft (6.1 m)
Maximum unsupported chimney length
between the offset and return
6 ft (1.83 m)
Maximum unsupported chimney height above
the replace
35 ft (10.67 m)
Maximum unsupported chimney above roof 6 ft (1.83 m)
WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and re.
Determine the chimney components needed to complete
your particular installation:
Measure the total vertical height of the fireplace
installation from the base of the replace assembly to
the approximate location of the bottom of the termination
cap.
Subtract the effective height of the replace assembly
(see Figure 8.2) from the total vertical height to determine
the overall height of the chimney installation.
Create a schematic for your application similar to Figure
8.2 showing components required (referring to Table
8.1). Figure 8.1 identies those components and where
used.
Install a ceiling restop whenever the chimney penetrates
a oor/ceiling.
NOTICE: A maximum of two pairs of offsets and returns
may be used.
CAUTION! Risk of Fire and/or Asphyxiation! DO
NOT connect this replace to a chimney ue servicing
another appliance. DO NOT connect to any air distribu-
tion duct or system. These actions could cause over-
heating/re in the chimney ue, or release of exhaust
fumes into the living areas.
Heatilator • CL36D, CR36D • 12538 • Rev Z 7/12
HEIGHT OF CHIMNEY COMPONENTS in. mm
Chimney Stabilizer
SL3 4-3/4 121
Ceiling Firestops
FS338 0 0
FS339 0 0
FS340 0 0
Offsets/Returns
SL315 13-3/8 340
SL330 15-1/2 394
Roof Flashing
RF370 0 0
RF371 0 0
Chimney Sections*
SL306 4-3/4 121
SL312 10-3/4 273
SL318 16-3/4 425
SL324 22-3/4 578
SL336 34-3/4 883
SL348 46-3/4 1187
* Dimensions reect effective height.