Heatiator CL36D Gas Heater User Manual


 
16
Marginal Location:
• Below peak
Location NOT recommended:
• Not the highest point of the roof
• Wind loading possible
Multi-level Roofs
Windward
Leeward
Recommended Location:
• Above peak
Recommended:
• Insulated exterior chase
in cooler climates
Recommended Location:
• Above peak
• Inside heated space
Location NOT recommended:
• Too close to tree
• Below adjacent structure
• Lower roof line
• Avoid outside wall
Marginal Location:
Wind loading possible
Figure 5.2 Recommended Chimney Locations
E. Locating Fireplace & Chimney
Location of the replace and chimney will affect perfor-
mance.
Install within the warm airspace enclosed by the building
envelope. This helps to produce more draft, especially
during lighting and die-down of the re.
Penetrate the highest part of the roof. This minimizes
the effects of wind loading.
Locate termination cap away from trees, adjacent
structures, uneven roof lines and other obstructions.
Minimize the use of chimney offsets.
Consider the replace location relative to oor and ceiling
and attic joists.
Take into consideration the termination requirements in
Section 8 and Section 9.
NOTICE: Locating the replace in a basement or in a location
of considerable air movement can cause intermittent smoke
spillage from replace. Do not locate replace near:
frequently open doors
central heat outlets or returns
Heatilator • CL36D, CR36D • 12538 • Rev Z 7/12