Performance Data
Model GLC Hot Gas Defrost | 60 Hz
Model
Capacity Fan Data
10°F TD
-20°F SST
6°C TD
-29°C SST
No. CFM m
3
H
BTUH Watts
6 Fins Per Inch
GLC035 3,500 1,025 1 700 1,189
GLC040 4,000 1,170 1 700 1,189
GLC047 4,700 1,380 1 650 1,104
GLC065 6,500 1,900 2 1,400 2,379
GLC075 7,500 2,200 2 1,300 2,209
GLC090 9,000 2,640 2 1,300 2,209
GLC120 12,000 3,520 3 2,100 3,568
GLC140 14,000 4,100 3 1,950 3,313
GLC160 16,000 4,690 4 2,600 4,418
GLC180 18,000 5,280 4 2,600 4,418
GLC200 20,000 5,860 5 3,250 5,522
GLC240 24,000 7,030 6 3,900 6,627
GLC280 28,000 8,200 6 3,900 6,627
4 Fins Per Inch
GLC041 4,100 1,200 1 690 1,172
GLC068 6,800 2,000 2 1,380 2,345
GLC080 8,000 2,340 2 1,380 2,345
GLC102 10,200 2,990 3 2,170 3,687
GLC136 13,600 3,990 4 2,760 4,690
GLC170 17,000 4,980 5 3,450 5,862
GLC204 20,400 5,980 6 4,140 7,035
GLC235 23,500 6,880 6 4,140 7,035
Model GLC Hot Gas Defrost | 50 Hz
Model
Capacity Fan Data
10°F TD
-20°F SST
6°C TD
-29°C SST
No. CFM m
3
H
BTUH Watts
6 Fins Per Inch
GLC035 3,325 974 1 630 1,070
GLC040 3,800 1,113 1 630 1,070
GLC047 4,465 1,308 1 586 995
GLC065 6,175 1,809 2 1,260 2,142
GLC075 7,125 2,087 2 1,170 1,989
GLC090 8,550 2,504 2 1,170 1,989
GLC120 11,400 3,339 3 1,891 3,213
GLC140 1,950 3,313 3 1,756 2,984
GLC160 2,600 4,418 4 2,341 3,978
GLC180 2,600 4,418 4 2,341 3,978
GLC200 3,250 5,522 5 2,927 4,973
GLC240 3,900 6,627 6 3,512 5,967
GLC280 3,900 6,627 6 3,512 5,967
4 Fins Per Inch
GLC041 690 1,172 1 621 1,056
GLC068 1,380 2,345 2 1,243 2,111
GLC080 1,380 2,345 2 1,243 2,111
GLC102 2,170 3,687 3 1,954 3,320
GLC136 2,760 4,690 4 2,485 4,223
GLC170 3,450 5,862 5 3,107 5,279
GLC204 4,140 7,035 6 3,728 6,334
GLC235 4,140 7,035 6 3,728 6,334
For EC motors, use 60 Hz capacity and airflow values (Units with EC motors
operating at 50 Hz will not see a reduction in performance due to the electronic
control of the motor)
NOTE: When using the hot gas units with a hot gas
loop drain pan on 0°F applications and below, an
insulated drain pan is required.
Capacity Correction Factors For
Electric and Hot Gas Defrost Units
Saturated Suction
Temperature °F
+20 -10 -20 -30
Saturated Suction
Temperature °C
-7 -23 -29 -34
Multiply Capacity
By
1.15 1.04 1.00 0.90