The standard design for the Chandler Low Prole Evaporator incorporates a hot gas loop in the drain pan. Utilizing
a hot gas loop is ideal for hot gas defrost applications where high temperature gas can be maintained to defrost
both the evaporator drain pan and coil.
For applications where cooler (lower) temperature hot gas is used for defrosting, Chandler oers optional electric
heater elements in the drain pan to ensure quick and ecient defrost of the drain pan allowing condensate to
drain quickly, saving the hot gas for ecient evaporator coil defrost.
If the optional electric heating element drain pan is preferred, please specify when ordering, there is no additional
charge.
Physical Data
Model GLC Hot Gas Defrost
Model
No. of
Fans
Connections (in.)
Approx.
Net Wt.
Coil
Inlet
ODF
Suction
ID
External
Equalizer
OD
Drain
MPT
Side
Port
OD
Hot Gas
Pan Conns.
OD
lbs. kg
6 Fins Per Inch
GLC035 1 5/8 5/8 1/4 3/4 3/8 5/8 26 12
GLC040 1 5/8 5/8 1/4 3/4 3/8 5/8 28 13
GLC047 1 5/8 5/8 1/4 3/4 3/8 5/8 31 15
GLC065 2 5/8 5/8 1/4 3/4 3/8 5/8 45 21
GLC075 2 5/8 7/8 1/4 3/4 3/8 5/8 47 22
GLC090 2 7/8 7/8 1/4 3/4 3/8 5/8 50 23
GLC120 3 7/8 7/8 1/4 3/4 3/8 5/8 62 29
GLC140 3 7/8 7/8 1/4 3/4 3/8 5/8 64 30
GLC160 4 7/8 1-1/8 1/4 3/4 3/8 5/8 83 38
GLC180 4 1-1/8 1-1/8 1/4 3/4 3/8 5/8 86 40
GLC200 5 1-1/8 1-1/8 1/4 3/4 3/8 5/8 103 47
GLC240 6 1-1/8 1-1/8 1/4 3/4 3/8 5/8 123 56
GLC280 6 1-1/8 1-1/8 1/4 3/4 3/8 5/8 126 57
4 Fins Per Inch
GLC041 1 5/8 5/8 1/4 3/4 3/8 5/8 30 14
GLC068 2 5/8 7/8 1/4 3/4 3/8 5/8 46 21
GLC080 2 5/8 7/8 1/4 3/4 3/8 5/8 49 23
GLC102 3 7/8 7/8 1/4 3/4 3/8 5/8 61 28
GLC136 4 7/8 1-1/8 1/4 3/4 3/8 5/8 82 38
GLC170 5 7/8 1-1/8 1/4 3/4 3/8 5/8 102 47
GLC204 6 7/8 1-1/8 1/4 3/4 3/8 5/8 122 56
GLC235 6 1-1/8 1-1/8 1/4 3/4 3/8 5/8 125 57