Heat & Glo LifeStyle XLR-N-CE Indoor Fireplace User Manual


 
39Heat & Glo • XLR-N-CE, XLR-PB-CE • 2198-900 Rev. J • 5/12
SCREWS
CAULK
STORM
COLLAR
(1of3)
Figure10.15
TERMINATIONCAP
H. InstallVerticalTerminationCap
• Attach the vertical termination cap by sliding the inner
collar of the cap into the inner ue of the pipe section
while placing the outer collar of the cap over the outer
ue of the pipe section.
• Secure the cap by driving three self-tapping screws
(supplied) through the pilot holes in the outer collar of the
cap into the outer ue of the pipe (see Figure 10.15).
Figure10.16WallThimble
I. InstallDecorativeWallComponents
A decorative wall thimble can be installed on wall through
which the vent passes. The decorative wall thimble is used
to cover the restop.
• Slide the decorative wall thimble over the last section of
horizontal pipe before connecting the termination cap to
the pipe.
• Once the pipe section and the termination cap have been
connected, slide the wall thimble up to the interior wall
surface and attach with screws provided. See Figure
10.16.
ImportantNotice: Heat shields may not be eld constructed.
J. HeatShieldRequirementsforHorizontal
Termination
WARNING! Risk of Fire! To prevent overheating and re,
heat shields must extend through the entire wall thick-
ness.
DO NOT remove the heat shields attached to the
wall shield restop and the horizontal termination cap
(shown in Figure 10.17).
• Heat shields must overlap 3,8 cm minimum.
There are two sections of the heat shield. One section is
factory-attached to the wall shield restop. The other sec-
tion is factory-attached to the cap. See Figure 10.17.
If the wall thickness does not allow the required 3,8 cm
heat shield overlap when installed, an extended heat
shield must be used.
• If the wall thickness is less than 11,1 cm, the heat shields
on the cap and wall shield restop must be trimmed. A
minimum 3,8 cm overlap MUST be maintained.
• Use an extended heat shield if the nished wall thick-
ness is greater than 18,4 cm.
• The extended heat shield may need to be cut to length
maintaining sufcient length for a 3,8 cm overlap be-
tween heat shields.
• Attach the extended heat shield to either of the existing
heat shields using the screws supplied with the extend-
ed heat shield. Refer to vent components diagrams in
the back of this manual.
• Rest the small leg on the extended heat shield on top of
the pipe section to properly space it from the pipe sec-
tion.