C. InstalltheCeilingFirestop
A ceiling restop MUST be used between
oors and attics.
SLPpipeonly - Frame opening 22,86 cm
x 22,86 cm whenever the vent penetrates
a ceiling/floor (see Figure 8.3).
• Frame the area with the same sized lumber
as used in ceiling/oor joist.
• The ceiling restop may be installed above or
below the ceiling joists when installed with a
attic insulation shield. It must be under joists
between oors that are not insulated. Refer
to Figure 8.4.
• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-
lation around the vent. Insulation must be kept
back from the pipe to prevent overheating.
Figure8.3 InstallingCeilingFirestop
ATTIC ABOVE
A
PIPE
SLP
A
22,95 cm
A
Figure8.4InstallingtheAtticShield
3 FASTENERS
PER SIDE
INSTALL ATTIC INSULATION SHIELDS
BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
CEILING FIRESTOP
INSTALLED BELOW CEILING
CEILING FIRESTOP
INSTALLED ABOVE CEILING