Heat & Glo LifeStyle SLR32 Indoor Fireplace User Manual


 
25
Heat & Glo • SLR32 • 2269-900 Rev. E • 4/12
Figure 7.4
Top Vent - Horizontal Termination
Venting with 1 elbow
H
1
V
1
V Minimum
H
1
Maximum
SLR32
90 Elbow 1-1/2 ft. 457 mm
1 ft. 305 mm 3 ft. 914 mm
2 ft. 610 mm 5 ft. 1.5 m
3 ft. 914 mm 7 ft. 2.1 m
4 ft. 1.2 m 14 ft. 4.3 m
H MAX. =14 ft. (4.3 m)
V + H MAX. = 40 ft. (12.2 m)
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
ALWAYS maintain speci ed clearances around venting and restop systems.
Install wall shield and ceiling restops as speci ed.
Failure to keep insulation or other material away from vent pipe may cause re.
WARNING
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when using
ex vent except when using the
simple up and out installation
(see Figure 7.3).