Heat & Glo LifeStyle GRAND-XTS Boiler User Manual


 
Heat & Glo • Supreme-XTS, Grand-XTS • 349-901 Rev. i • 12/09
8
Fire Risk.
Asphyxiation Risk.
Terminations MUST meet minimum clearances.
Exhaust gases are hot.
Nearby vents may draw fumes into house.
A. Vent Termination Minimum Clearances
Figure 4.1 speci es minimum vent heights for various
pitched roofs.
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 4.1 Minimum height from roof to lowest discharge
opening
4
4
Termination Locations
* 3 foot minimum in snow regions
WARNING
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING