Heat & Glo LifeStyle EM-485T - 42 Indoor Fireplace User Manual


 
35
Heat & Glo • EM-415, EM-485 • 33056 • Rev AF 7/12
Chimney
Pipe
Chase Top
Termination Cap
Chase
Collar
2 in. (51 mm)
Minimum Height
Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm).
Place waterproof sealer under
each flange of the termination
cap and on top of each screw
to help prevent leaks.
2 in. (51 mm)
maximum
4 3/4 in. (121 mm)
maximum
The last section of pipe must
stop between 2 in. (51 mm)
above the top of the chase and
4 3/4 in. (121 mm) below the
top of the chase.
Figure 9.7 Installing a TS345/TS345P Square Termination Cap
TS345/TS345P Square Termination Cap
Chimney
Pipe
Chase Top
Termination Cap
Chase
Collar
2 in. (51 mm)
Minimum Height
Remove 2 screws
from front & back
to lift the top off
Termination cap pipe and chimney section must overlap
1-1/2 in. (38 mm)
Place waterproof sealer
under each flange of the
termination cap and on
top of each screw to
help prevent leaks.
The last section of pipe
must stop between 2 in.
(51 mm) above top of
chase and 7 in. (178 mm)
below top of chase
2 in. (51 mm)
7 in. (178 mm)
Figure 9.8 Installing a TCT375 Terra Cotta Cap
TCT375 Terra Cotta Cap