Heat & Glo LifeStyle DAKOTA-AU Indoor Fireplace User Manual


 
Heat & Glo Lifestyle Collection • Dakota-AU• 4036-914 Rev B • 06/07 11
A. Mantel Projections
Figure 7.1 shows the minimum vertical dimension of replace mantels or other combustible projections above the top front
edge of the replace.
Mantel
B
A
2.13 m
minimum
ceiling height
Overhang
305 mm
max. combustible
mantel depth
Figure 7.1 Clearances to Combustible Mantels or other Combustibles above Fireplace
7
7
Finishing
If A is:
Then B must
be at least:
152 mm - 914 mm 660 mm
915 mm or more 457 mm