Heat & Glo LifeStyle CERONA-42 Gas Heater User Manual


 
Heat & Glo • Cerona-36, Cerona-42 • 2106-900 Rev. A • 6/06
15
Cerona-36 ONLY >
Figure 5.3
Figure 5.4
D. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling firestops.
ALWAYS maintain specified clearances around venting and firestop systems.
Install
wall shield and ceiling firestops as specified.
Failure to keep insulation or other material away from vent pipe may cause fire.
WARNING
1. Top Vent - Horizontal Termination
One Elbow
Two Elbows
V
1
Minimum H
1
+ H
1
Maximum
0.5 ft 152 mm 2 ft 610 mm
1 ft 305 mm 2 ft 610 mm
2 ft 610 mm 5 ft 1.5 m
3 ft 914 mm 8 ft 2.4 m
4 ft 1.2 m 11 ft 3.4 m
5 ft 1.5 m 14 ft 4.3 m
6 ft 1.8 m 17 ft 5.2 m
7 ft 2.1 m 20 ft 6.1 m
8 ft 2.4 m 23 ft 7.0 m
V
1
+ H
1
+ H
2
= 63 ft (19.2 m) Maximum
H
1
+ H
2
= 23 ft (7.0 m) Maximum
V
1
H
1
H
2
H
1
V
1
INSTALLED
HORIZONTALLY
NOTE: Must have
a minimum verti-
cal vent before at-
taching a 90
o
el-
bow to the unit.
See chart.
Cerona-36 ONLY >
V
1
Minimum H
1
Maximum
0.5 ft 152 mm 2 ft 610 mm
1 ft 305 mm 2 ft 610 mm
2 ft 610 mm 5 ft 1.5 m
3 ft 914 mm 8 ft 2.4 m
4 ft 1.2 m 11 ft 3.4 m
5 ft 1.5 m 14 ft 4.3 m
6 ft 1.8 m 17 ft 5.2 m
7 ft 2.1 m 20 ft 6.1 m
8 ft 2.4 m 23 ft 7.0 m
V
1
= 40 ft (12.2m) Maximum
H
1
= 23 ft (7.0 m) Maximum
V
1
+ H
1
= 63 ft (19.2m) Maximum
Minimal Vertical Vent
Model ft. mm
Cerona-36
0.5 152
Cerona-42
1305
NOTE: Must have
a minimum verti-
cal vent before at-
taching a 90
o
el-
bow to the unit.
See chart.
Minimal Vertical Vent
Model ft. mm
Cerona-36
0.5 152
Cerona-42
1305