Fire Risk.
Hearth extension required to protect
combustible oors in front of appliance.
An 8 inch minimum hearth extension must be constructed
of non-combustible material.
E. Hearth Extension
WARNING
Figure 3.6 Hearth Extension Dimensions
AB
Cerona-36
in. 41-1/8 8
mm 1045 203
Cerona-42
in. 48-1/8 8
mm 1222 203
A
B
NAILING TABS
(BOTH SIDES)
NON-COMBUSTIBLE
HEARTH EXTENSION
1 in. max.
(25 mm)
8 in. min.
(203 mm)
COMBUSTIBLE
SURFACE
MARBLE, GRANITE, TILE OR
OTHER NON-COMBUSTIBLE
HEARTH EXTENSION
BOTTOM OF
FIREPLACE
Figure 3.7 Fireplace sitting on combustible surface.
Figure 3.8 Fireplace raised a minimum of 6 inches away from
combustible surface.
BOTTOM OF
FIREPLACE
SURFACE MAY BE COMBUSTIBLE
COMBUSTIBLES
UP TO 1 INCH
THICK ALLOWED
UNDER THE OPENING
6 INCHES
MINIMUM
1 INCH MAX.
TO ALLOW FOR
DOOR CLEARANCE
The base of the replace may sit on a combustible surface.
The area in front of the replace must be protected by a
noncombustible hearth extension, unless the replace is
raised a minimum of 6 inches above the combustible oor
or hearth. See gures 3.7 and 3.8.