Part 4 Trouble Shooting
7. Self-diagnosis Function
Error Indicator
The error indicator assists with self-diagnoisis of the air conditioner and identifies if there is any trouble.
The error indicator location is near the ON/OFF button by the LED on the evaporator and will signal as shown in
the table below.
If more than two errors occur simultaneously, primarily the highest severity error code is displayed.
After error an occurrence, the error is cleared, the error LED is also cleared, simultaneously.
To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
The error codes are different for various models
9, 12kBtu/h Model
1 time
1
time
3
sec
2
times
2times
3
sec
4times
4
times
3 sec
5times
5times
3 sec
6
times
6
times
3
sec
7
times
7
times
3
sec
3
sec
3
sec
2
times
3
sec
2
times
3
sec
1
time
3
sec
1
time
3
sec
1
time
3 sec
1
2
4
5
6
7
Error Indicator
Error
Code
Cause of Error
Display
Indoor Outdoor
Indoor
Operation
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
Indoor Temp. sensor error
- Sensor open or short
Heat Sink sensor error
- Sensor open or short
- Heat Sink temp is over 95˚C
(203˚F)
Communication error
Outdoor Temp. sensor error
- Sensor open or short
DC Peak error
Over current error (CT2)
ON
ON
ON
OFF
SHUT
DOWN
SHUT
DOWN
9times
9
times
3
sec
10times
10
times
3 sec
10
ON
Outdoor fan lock error
Discharge pipe thermistor is
short or open.
(BLDC fan model only)
OFF
8times 8times
3
sec
8
Indoor fan lock error
(BLDC fan model only)
OFF
9
(4 LED Model)