Part 2 Functions & Controls
5.8 Overheating Protection (Power Module)
5.8.1 9,12kBtu/h Model
If the temperature of the heat sink thermistor reaches over Toff, the Compressor stop instantly.
The compressor operating frequency is limited according to the heat sink thermistor. (refer to below FIG.)
The LED on PCB board will blink 4 times, when the thermistor is open or short, also when the temperature is over T
off.
T off °C
T2 °C
Heat Sink Temp.
T1 °C
T on °C
COMP
Freq.
Free OFF FreeFc-1 Fc-1Fc-2 Fc-2
T = (T off - T on)/3
T1 = T on + T
T2 = T on + 2
*
T
T on : 85°C(185°F) (Model by Model)
T off : 95°C(203°F) (Model by Model)