Heat Controller VMC30SB-1/VMH30SB-1 Heat Pump User Manual


 
- 25 -
Only for training and service purposes
Part 2 Functions & Controls
5.10 DC Peak control
5.10.1 DC Peak Current Error by a fault signal of IPM
If the operating current of IPM reaches 35A 3A, the compressor stops instantly.
If DC PEAK occurs 5 times within 1 hour, the appliance turns off and displays Error Code 6(9,12kBtu/h Model) / Error
Code 21(18,24,30kBtu/h Model).
5.10.2 DC Peak Current Error by the compressor lock
If the DC LINK voltage is below DC 140V and this occurs 5 times within 1 hour while the compressor is operating, the
appliance turns off and display Error Code 6(9k,12k Model) / Error Code 23(18k,24k,30k Model).
5.10.3 DC Peak Current Error by the Outdoor Fan Lock
If this problem occurs 5 times within 1 hour in case of the temperature of outdoor pipe thermistor is over 65°C(149°F)
while the compressor is operating, the appliance turns off and displays Error Code 6(9,12kBtu/h Model) / Error Code
61(18,24,30kBtu/h Model).
5.11 Discharge Pipe Temp Control
5.11.1 9,12kBtu/h Model
If the temperature of the discharge pipe of compressor reaches over 130°C(266°F) or below -30°C(-22°F) the com-
pressor stops instantly.
The compressor's operating frequency is limited according to the compressor dome thermistor. (Refer to below Fig.)
Temperature range of COMP SPEC varies by 10°C(50°F).
T off : 110°C(230°F)
T2 : 100°C(212°F)
Discharge pipe temp.
COMP Freq. Free Free
Fh min
OFFFc-1 Fc-1Fc-2 Fc-2
T = (T off - T2)/2
T1 = T2 - 2
*
T
T3 = T2 + T
T off °C
T2 °C
T3 °C
T1 °C
-13 °C(8.6°CF)