Heat Controller VMC30SB-1/VMH30SB-1 Heat Pump User Manual


 
- 14 -
Only for training and service purposes
Part 2 Functions & Controls
4.6.2 Sleep timer operation for heating cycle Heatpump Only
While in heating mode, 60 min. after the start of the sleep timer, the setting temperature decreases by 1 C(2 .
After another 60minutes lapse, it decreases again by 1°C(2 .
4.7 Auto restart
When the power comes back after a sudden power failure during operation, the mode before the power failure is kept
in the memory of the appliance appliance. Upon restoring power, The unit will return back to it's last operation mode
automatically based on the information saved in the appliance's memory, as shown below.
Operation mode that is kept on the memory
- State of operation ON/OFF
- Operation mode/setting temp./selected airflow speed
- Sleep timer mode/remaining time of sleep timer
- Chaos Swing
Setting temp. (°C)
Heating ON temp.
(Setting temp)
Heating OFF temp.
(Setting temp. +4.0°C(+8°F))
1 2 Sleep time
(
hr
)
1.0°C(2°F) down
1.0°C(2°F) down