Hearth and Home Technologies EXCLAIM-36 Indoor Fireplace User Manual


 
43
D. Finishing Material
Refer to Sections 11.A. and Sections 11.B. for combus-
tible/noncombustible materials. Refer to Figure 11.9 for
noncombustible zone.
WARNING! Risk of Fire!
You must maintain clearances.
Use only non-combustible framing material below
standoffs.
Sheetrock, wood or other combustibles must NOT be
used as sheathing or facing in the noncombustible
zone.
DO NOT cover metal replace front with combustible
materials.
Install combustible materials only to speci ed clearances
on top front and side edges.
These surfaces
may be covered
with non-combustible
material.
Non-combustible
sealant.
Figure 11.9 Noncombustible Facing
Metal strips are placed 2 in. (51 mm)
under the front of the fireplace and must
extend beyond the front and sides of
fireplace opening by 2 in. (51 mm)
Continuous,
non-combustible sealant
Floor constructed of wood or
other combustible material
HX4 Hearth Ext
or equivilent
insulation
Finished combustible wall
Combustible material
Non-combustible
decorative facing
(up to full brick depth)
2 x 4 header, flush with
front of stand-offs
Tile, stone or other
non-combustible material
Flat 2 x 4 stud wall
Figure 11.10 Decorative Facing
Heat & Glo • EXCLAIM-36, EXCLAIM-42 • 4013-251 Rev C • 11/08