Hearth and Home Technologies EXCLAIM-36 Indoor Fireplace User Manual


 
27
A. Chimney Requirements
Measure vertical distances from the base of the replace
as shown in Figure 8.2.
6 ft (1.8 m) max.
unsupported run
20 ft (6 m) max.
pipe between an
offset & return
Ceiling Firestop
35 ft (10.7 m)
max. straight
unsupported
chimney height
18.5 ft (5.6 m) min. height
single offset-return
24 ft. (7.3 m) min. height
double offset-return
90 ft (27.4 m) max. height
6 ft (1.8 m) max.
unsupported chimney
above roof
55-1/2 in.
(1410 mm)
Effective Height
(bottom of fireplace
to top of starter collar)
11-10 in./279-254mm
adaptor required in
Canada
Figure 8.2 Chimney Requirements
Table 8.1
ft m
Minimum overall straight height 18 5.49
Minimum height with offset/return 18.5 5.64
Maximum height 90 27.43
Maximum chimney length between an
offset and return
20 6.10
Maximum distance between chimney
stabilizers`
35 10.67
Double offset/return minimum height 24 7.32
Maximum unsupported chimney length
between the offset and return
6 1.83
Maximum unsupported chimney height
above the replace
35 10.67
Maximum unsupported chimney above
roof
6 1.83
WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and re.
Determine the chimney components needed to complete
your particular installation:
Measure the total vertical height of the fireplace
installation from the base of the replace assembly to
the approximate location of the bottom of the termination
cap.
Subtract the effective height of the replace assembly
(see Figure 8.2) from the total vertical height to determine
the overall height of the chimney installation.
Create a schematic for your application similar to Figure
8.2 showing components required (referring to Table
8.1). Figure 8.1 identi es those components and where
used.
Install a ceiling restop whenever the chimney penetrates
a oor/ceiling.
NOTICE: A maximum of two pairs of offsets and returns
may be used.
CAUTION! Risk of Fire and/or Asphyxiation! DO
NOT connect this replace to a chimney ue servicing
another appliance. DO NOT connect to any air distribu-
tion duct or system. These actions could cause over-
heating/ re in the chimney ue, or release of exhaust
fumes into the living areas.
Heat & Glo • EXCLAIM-36, EXCLAIM-42 • 4013-251 Rev C • 11/08
HEIGHT OF CHIMNEY COMPONENTS in. mm
US Canada ONLY
Chimney Stabilizer
SL11 SL4 4-3/4 121
Ceiling Firestops
FS538 FS538 0 0
FS540 FS540 0 0
Offsets/Returns
SL1130 SL430 14-1/2 368
Roof Flashing
RF570 RF570 0 0
RF571 RF571 0 0
Chimney Sections*
SL1106 SL406 4-3/4 121
SL1112 SL412 10-3/4 273
SL1118 SL418 16-3/4 425
SL1136 SL436 34-3/4 883
SL1148 SL448 46-3/4 1187
n/a SLA10 16-3/4 425
* Dimensions re ect effective height.