Hearth and Home Technologies BE-36-CIPI Indoor Fireplace User Manual


 
Hearth & Home Technologies • BE-36-C, BE-36-CIPI • 397-981 Rev. R • 2/05
16
STRAIGHT UP
VERTICAL VENTING
V (FT.)
45' MAX.
Figure 8. Straight up Vertical Venting
Use SL D-Series
components only.
NOTE: For vertical
venting over 20 feet an
Extended Vertical Baffle
Kit is recommended for
improved flame
appearance.
V
CAP
Figure 7.
Flex Vent
The flex vent must be supported with the spacing between
support intervals not exceeding 4 feet, with no more than ½
inch sag between supports.
A support is required at each change in venting direction,
and in any location where it is necessary to maintain the
necessary clearance to combustibles. A simple “up and out”
installation (Figure 7) requires only enough support to main-
tain the necessary clearance to combustibles. However, the
vent attachment point and the firestop location are consid-
ered to be supports.
3” CLEARANCE
TERMINATION
CAP
FLEX-VENT
1”
CLEARANCE
STRAIGHT OUT HORIZONTAL VENTING
H
Max. Run
36" (914 mm)
Use DVP-Series
components only.
Figure 9. Straight Out Horizontal Venting
For corner
installation.
45-DEGREE
ELBOW
H
Two 90
0
elbows or one 45
0
elbow may be used for corner
installations. The use of two 90
0
elbows in a corner installation
will affect space requirements
(see Fig. 2)
90-DEGREE
ELBOWS