Haier HSU-09HS03/R2DB Air Conditioner User Manual


 
according to the heat-exchange temperatures as shown in the table below.
High Work-intense protection control:
Picture 12.1
Heat-exchange temperature frequency values
when the high work-intense starts
THHEAT6 74.7
THHEAT5 70.3
THHEAT4 65.1
THHEAT3 62.2
THHEAT2 52.9
THHEAT1 51.6
THHEAT0 47.1
Indicated
frequency
C D E D C B A B C D E
Normal idle mode stop
High Work-intense protection
High Work-intense protection
alarm
.
High Work-intense protection alarm will start if there are two times of high work-intense
protection within 30 minutes.
. If the heat-exchange temperature does not reach THHEAT [2], it will resume to
the normal temperature level control
. The smaller one of the high work-intense frequency and level frequency will be
the operation data.
11. Low-temperture treatment for Heating mode
If the four-way valve can not switch or when the none-frost-removing
compressor starts again under the heating mode if the heat-exchange temperature
remains under"THHOTLTH" -4.5 for 90 seconds, the compressor will start 3
minutes of idle mode and start again when the heat-exchange temperature is
above " THHOTLTH " -4.5
12. Remote control
. Start or stop running with the remote-control signals.
. Only OFF signal is accepted when there are emergencies or malfunctions.
1 second delay: Starting, stopping and signals except the wind direction signal all
begins 1 second after the receiption of the signal.
13.EEPROM control
. EEPROM is wrong when the EEPROM parameter sum does not accord with the
check sum after the outdoor unit is powered on.
. The outdoor unit EEPROM is wrong will be displayed when the indoor unit
32
Model:
HSU-12HS03/R2(DB)
HSU-09HS03/R2(DB)Domestic Air Conditioner