Haier HSU-09HS03/R2DB Air Conditioner User Manual


 
Frequency control form for wind volume
Limited frequency
variables
Limited frequency
Medium wind volume
FQLIMMD
Weak wind volume FQLIMLO
When judging the conditions for frequency limit under the heating mode, first
judge if the unit has been set to weak wind volume mode. If it has been set to one
mode, then follow the table below for the limit modification.
Outdoor temperature
condition
Indicated frequency
011 (Below 20 ) Limited frequency for weak
010(15-20 ) Limited frequency for weak
001(10-15 ) Limited frequency for weak
000(below10 ) Normal frequency
3. Indoor blower fan control
3-0-1. Targeted running speed
Model 09
Running speed variable
running speed
rpm
Slightly weak FRPMTBL00
SSLO silent SSLO
FRPMTBL01
Weak FRPMTBL02
Strong FRPMTBL05
Weak FRPMTBL04
Heating
Aut
oma
tic
Strong FRPMTBL05
Slightly weak FRPMTBL06
SSLO silentSSLO
FRPMTBL07
Weak FRPMTBL08
Strong FRPMTBL11
Weak FRPMTBL10
Cooling
Aut
oma
tic
Strong FRPMTBL11
Weak FRPMTBL12
Ventilatio
n
Strong FRPMTBL13
Cooling FRPMTBL09
Quota
Heating FRPMTBL03
. When the wind volume is manually medium, the running speed is
(strong+weak)/2.
When it is automatically medium, the running speed is (strong automatic+ weak
automatic)/2(not counted if it is not up to 10rpm)
27
Model:
HSU-12HS03/R2(DB)
HSU-09HS03/R2(DB)Domestic Air Conditioner