Haier HSU-09HS03/R2DB Air Conditioner User Manual


 
3-1.heat running
3-1-1. Warm boot
When the heat running starts or the frost removing ends and the compressor starts
again, in order to avoid cold wind, warm boot wind volume control should be done.
Heat exchange temperature
THHOT3
37.0
THHOT2
35.2
THHOT1
25.2 4 minutes
THHOTR
16
Stop slightly weak weak setting weak slightly weak stop
To control the indoor blower fan as shown in the table above according to the heat
exchange temperature
When the heat exchange temperature rises to the level between THHOT1 and
THHOT2 and even after 4 minutes it cannot reach the level between THHOT2 and
THHOT3, enter into the next level without referring to the heat exchange
temperature.
the blower fan stops when the heat exchange temperature is below 25
the blower fan is working slightly weak when he heat exchange temperature is
above 25 and below 35
the blower fan is working weak if the he heat exchange temperature remains 35
for less than 4 minutes.
The blower fan works as set if the he heat exchange temperature remains 35 for
more than 4 minutes
the blower fan works as set if the he heat exchange temperature remains above
37
3-1-2. When the compressor stops and remains idle for 3 minutes
20 seconds after the compressor stops, the wind volume is weak(switching to
SSLO in silent running mode)and then slightly weak.
If the compressor stops when the heat running starts, the wind volume is weak
3-1-3. Restart of the compressor
The wind volume is set by the remote-controler after the warm boot.
.select the wind volume by the temperature in the automatic wind volume mode
28
Model:
HSU-12HS03/R2(DB)
HSU-09HS03/R2(DB)Domestic Air Conditioner