PRODUCT DESIGN
5
36"
36"
24"
P
L
E
N
U
M
U
N
I
T
P
L
A
T
F
O
R
M
C
U
R
B
Rooftop Installation - Horizontal (H)
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
In installations where the unit is installed above ground level
and not serviceable from the ground (Example: roof top in-
stallations) the installer must provide service platform for ser-
vice person with rails or guards in accordance with local codes
or ordinances, or, in their absence, with the latest edition of
the Uniform Mechanical Code Section 305.
WARNING
TO PREVENT POSSIBLE PROPERTY DAMAGE, THE
UNIT SHOULD REMAIN IN AN UPRIGHT POSITION
DURING ALL RIGGING AND MOVING OPERATIONS.
TO FACILITATE LIFTING AND MOVING IF A CRANE IS
USED, PLACE THE UNIT IN AN ADEQUATE CABLE
SLING.
Refer to Roof curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the
National Roofing Contractors Association Manual.