Goodman Mfg SS-CPG36-72 Air Conditioner User Manual


 
ProdUCt sPeCiFiCations
ProdUCt sPeCiFiCations
28 www.goodmanmfg.com SS-CPG36-72
rooF CUrB installation (Cont.)
CurbinstallationsmustcomplywithlocalcodesandshouldfollowtheestablishedguidelinesoftheNationalRoongContractors
Association.
Properunitinstallationrequiresthattheroofcurbbermlyandpermanentlyattachedtotheroofstructure.Checkforadequate
fasteningmethodpriortosettingtheunitonthecurb.
Fullperimeterroofcurbsareavailablefromthefactoryandareshippedunassembled.Theinstallingcontractorisresponsiblefor
eldassembly,squaring,leveling,andmountingontheroofstructure.Allrequiredhardwarenecessaryfortheassemblyofthesheet
metalcurbisincludedinthecurbaccessorypackage.
• Determinesufcientstructuralsupportbeforelocatingandmountingthecurbandpackageunit.
• Duct-workmustbeconstructedusingindustryguidelines.Theduct-workmustbeplacedintotheroofcurbbeforemountingthe
packageunit.Ourfullperimetercurbsincludeductconnectionframestobeassembledwiththecurb.Cantilevered-typecurbs
arenotavailablefromthefactory.
• Contractorfurnishescurbinsulation,cantstrips,ashing,andgeneralroongmaterial.
• Supportcurbsonparallelsideswithroofmembers.Topreventdamagetotheunit,theroofmemberscannotpenetratesupply
andreturnductopenings.
Note:Theunitandcurbaccessoriesaredesignedtoallowverticalductinstallationbeforeunitplacement.Ductinstallationafterunit
placementisnotrecommended.
Seethemanualshippedwiththeroofcurbforassemblyandinstallationinstructions.
3-d view
14 x 20



70¾
40¼
14
1
5
/
6
¾
14
1⅜
Insulated
Panels
toP view