Goodman Mfg SS-CPG36-72 Air Conditioner User Manual


 
ProdUCt sPeCiFiCations
ProdUCt sPeCiFiCations
14 www.goodmanmfg.com SS-CPG36-72
airFlow data — CPG060B
standard direCt-drive — horizontal standard direCt-drive — down shot
    


   



1416 0.1 1.63 176 588
T1
1237 0.1 1.64 180 638
T1
1295 0.2 1.61 174 621 1191 0.2 1.75 194 682
1200 0.3 1.68 186 660 1127 0.3 1.80 200 715
1133 0.4 1.79 196 704 1065 0.4 1.89 214 753
1045 0.5 1.90 208 753 994 0.5 1.97 220 797
1543 0.1 2.00 220 627
T2
1437 0.1 2.13 248 687
T2
1485 0.2 2.12 236 671 1384 0.2 2.24 254 726
1425 0.3 2.20 250 698 1312 0.3 2.29 262 759
1352 0.4 2.26 258 748 1245 0.4 2.42 280 803
1304 0.5 2.39 274 786 1185 0.5 2.54 294 847
2107 0.1 4.02 502 797
T3
1988 0.1 4.49 558 885
T3
2031 0.2 4.13 518 819 1942 0.2 4.58 574 907
1980 0.3 4.27 536 858 1882 0.3 4.69 582 935
1954 0.4 4.37 554 880 1847 0.4 4.80 600 962
1887 0.5 4.48 572 913 1784 0.5 4.87 612 990
1839 0.6 4.58 582 940 1762 0.6 4.97 626 1008
1782 0.7 4.72 602 968 1688 0.7 5.05 642 1039
2224 0.1 4.73 592 832
T4
2106 0.1 5.14 650 924
T4
2165 0.2 4.79 612 860 2050 0.2 5.26 670 951
2123 0.3 4.91 630 891 1993 0.3 5.32 678 969
2079 0.4 5.01 642 913 1960 0.4 5.47 696 1001
2029 0.5 5.14 666 946 1920 0.5 5.54 706 1021
1978 0.6 5.26 676 969 1880 0.6 5.61 726 1041
1926 0.7 5.38 698 1001 1810 0.7 5.73 736 1072
1872 0.8 5.48 712 1028 1760 0.8 5.81 750 1093
1817 0.9 5.58 722 1056 1694 0.9 5.84 752 1122
2318 0.1 5.42 700 874
T5
2199 0.1 5.87 762 968
T5
2296 0.2 5.55 720 903 2146 0.2 5.96 772 989
2228 0.3 5.66 734 929 2121 0.3 6.06 788 1012
2193 0.4 5.76 748 950 2066 0.4 6.15 804 1039
2145 0.5 5.90 766 979 2010 0.5 6.21 814 1056
2097 0.6 5.99 784 1012 1978 0.6 6.32 834 1084
2054 0.7 6.10 798 1034 1919 0.7 6.28 830 1102
1991 0.8 6.15 810 1050 1837 0.8 6.22 814 1122
1952 0.9 6.26 826 1079 1738 0.9 6.04 786 1127

Assumes dry coil with lter in place; SCFM correcon for wet coil = 4%
Five-ton models are shipped from the factory with speed tap set on T4.