22
SPLIT SYSTEM HEATING PERFORMANCE
EXPANDED PERFORMANCE DATA
MODEL: GSH140421A* / CA*F4860D6A*+TXV / MBR2000**-1
HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 -5 -10
MBh 49.8 47.1 44.4 41.5
39.6
38.435.632.931.228.826.625.124.121.719.216.814.311.7
Delta T32.931.229.327.426.225.423.621.720.719.117.616.616.014.312.711.1 9.5 7.7
KW 3.20 3.14 3.08 3.02
2.99
2.96 2.91 2.85 2.89 2.83 2.77 2.73 2.71 2.65 2.59 2.53 2.46 2.40
AMPS 16.1 14.4 13.1 11.9 11.2 10.9 9.9 9.1 8.4 7.8 7.1 6.8 6.6 5.9 5.1 4.4 3.6 2.6
COP4.564.394.214.023.883.793.593.383.162.982.812.692.612.402.171.941.701.43
EER 15.6 15.0 14.4 13.7 13.3 13.0 12.3 11.5 10.8 10.2 9.6 9.2 8.9 8.2 7.4 6.6 5.8 4.9
HI PR 222 213 205 196 191 188 180 173 166 158 152 148 146 140 135 129 125 120
LO PR 82 76 71 66 62 60 55 49 44 39 35 32 31 26 23 19 17 13
Above information is for nominal CFM and 70 degree indoor dry bulb.
MODEL: GSH140481A* / CA*F4860D6A*+TXV / MBR2000**-1 HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 -5 -10
MBh 57.8 54.7 51.5 48.2
46.0
44.641.438.237.734.832.030.229.126.123.220.217.214.1
Delta T34.532.730.828.827.526.624.722.822.520.819.118.117.415.613.812.110.3 8.4
KW 4.02 3.94 3.86 3.79
3.74
3.71 3.64 3.56 3.62 3.54 3.46 3.41 3.38 3.30 3.22 3.14 3.06 2.98
AMPS 20.9 18.7 17.0 15.5 14.6 14.2 12.9 11.8 10.9 10.1 9.2 8.8 8.6 7.7 6.6 5.8 4.7 3.4
COP4.214.073.903.723.603.523.333.143.052.882.712.592.522.322.101.881.651.38
EER 14.4 13.9 13.3 12.7 12.3 12.0 11.4 10.7 10.4 9.8 9.3 8.9 8.6 7.9 7.2 6.4 5.6 4.7
HI PR 231 221 213 204 199 195 187 180 172 165 158 154 151 146 140 134 130 125
LO PR 76 70 66 60 57 55 51 45 41 36 32 30 29 24 21 18 15 12
Above information is for nominal CFM and 70 degree indoor dry bulb.
MODEL: GSH140601A* / CA*F4860D6A* +TXV / MBR2000**-1 HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 -5 -10
MBh 69.1 65.5 61.6 57.6
55.0
53.349.545.741.037.934.932.931.728.425.222.018.815.4
Delta T34.632.830.828.827.526.724.822.820.518.917.516.515.914.212.611.0 9.4 7.7
KW 4.21 4.12 4.04 3.96
3.91
3.87 3.79 3.71 3.71 3.62 3.54 3.49 3.45 3.36 3.28 3.20 3.11 3.02
AMPS 19.3 17.8 16.7 15.6 15.1 14.8 13.9 13.2 12.6 12.0 11.4 11.2 11.0 10.4 9.7 9.1 8.4 7.5
COP4.814.654.464.264.124.033.823.603.243.062.892.762.692.472.252.011.771.49
EER 16.4 15.9 15.2 14.6 14.1 13.8 13.1 12.3 11.1 10.5 9.9 9.4 9.2 8.5 7.7 6.9 6.0 5.1
HI PR 228 219 210 201 197 193 185 178 170 163 156 152 150 144 139 133 128 124
LO PR 74 68 64 59 55 53 49 44 39 35 31 29 28 23 20 17 15 12
Above information is for nominal CFM and 70 degree indoor dry bulb.
High pressure is measured at the suction service valve ( the larger valve). AMPS = Outdoor unit amps (comp.+fan)
Low pressure is measured at the gauge port connection. KW = Total system powe
r