EXPANDED PERFORMANCE DATA
MODEL: GSH140181A* / CA*F3131B6A*+TXV / MBR800**-1 HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10
MBh 22.6 21.4 20.2 18.8
18.0
17.4 16.2 14.9 13.6 12.5 11.5 10.9 10.5 9.4 8.3 7.3 6.2 5.1
Delta T 34.9 33.1 31.1 29.1 27.8 26.9 25.0 23.1 20.9 19.3 17.8 16.8 16.2 14.5 12.9 11.2 9.6 7.8
KW 1.56 1.53 1.50 1.47
1.46
1.44 1.41 1.38 1.38 1.35 1.32 1.30 1.28 1.25 1.22 1.19 1.16 1.13
AMPS7.16.56.15.85.65.55.24.94.74.54.34.24.13.93.73.53.22.9
COP 4.23 4.09 3.93 3.75 3.62 3.54 3.36 3.16 2.88 2.72 2.56 2.45 2.39 2.19 1.99 1.78 1.56 1.31
EER 14.5 14.0 13.4 12.8 12.4 12.1 11.5 10.8 9.8 9.3 8.8 8.4 8.2 7.5 6.8 6.1 5.3 4.5
HI PR 248 237 228 218 213 209 201 193 185 176 169 165 162 156 150 144 139 134
LO PR 82 76 71 66 62 60 55 49 44 39 35 32 31 26 23 19 17 13
Above information is for nominal CFM and 70 degree indoor dry bulb.
MODEL: GSH140241A* / CA*F3636B6A*+TXV / MBR800**1 HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 -5 -10
MBh 30.2 28.6 26.9 25.1
24.0
23.3 21.6 19.9 18.8 17.3 15.9 15.1 14.5 13.0 11.5 10.1 8.6 7.0
Delta T 32.9 31.1 29.3 27.4 26.1 25.3 23.5 21.7 20.4 18.9 17.4 16.4 15.8 14.2 12.6 11.0 9.4 7.7
KW 2.06 2.02 1.98 1.94
1.92
1.90 1.86 1.83 1.89 1.85 1.81 1.78 1.77 1.73 1.68 1.64 1.60 1.56
AMPS7.97.67.57.37.27.27.17.06.96.86.76.76.66.56.46.46.26.1
COP 4.30 4.14 3.98 3.79 3.66 3.58 3.39 3.19 2.91 2.74 2.58 2.47 2.40 2.21 2.00 1.79 1.57 1.32
EER 14.7 14.2 13.6 13.0 12.5 12.2 11.6 10.9 9.9 9.4 8.8 8.4 8.2 7.5 6.8 6.1 5.4 4.5
HI PR 227 218 209 200 195 192 184 177 169 162 155 152 149 143 138 132 127 123
LO PR 80 74 70 64 61 58 54 48 43 38 34 31 30 26 22 19 16 13
Above information is for nominal CFM and 70 degree indoor dry bulb.
MODEL: GSH140301A* / CA*F3636B6A* +TXV / MBR1200**-1
HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 -5 -10
MBh 34.7 32.8 30.9 28.9
27.6
26.7 24.8 22.9 20.9 19.3 17.8 16.8 16.2 14.5 12.9 11.2 9.6 7.8
Delta T 29.8 28.2 26.5 24.8 23.7 22.9 21.3 19.6 18.0 16.6 15.3 14.4 13.9 12.4 11.0 9.6 8.2 6.7
KW 2.24 2.20 2.16 2.12
2.09
2.08 2.04 2.00 2.06 2.02 1.98 1.95 1.93 1.89 1.85 1.80 1.76 1.72
AMPS9.68.98.47.97.67.57.16.76.46.25.95.75.75.45.04.84.44.0
COP 4.53 4.37 4.19 4.00 3.86 3.77 3.57 3.36 2.97 2.80 2.63 2.52 2.45 2.25 2.04 1.82 1.59 1.34
EER 15.5 14.9 14.3 13.7 13.2 12.9 12.2 11.5 10.1 9.6 9.0 8.6 8.4 7.7 7.0 6.2 5.4 4.6
HI PR 216 208 200 191 186 183 176 169 162 154 148 145 142 137 131 126 121 117
LO PR 80 74 69 64 60 58 53 47 43 38 34 31 30 25 22 19 16 13
Above information is for nominal CFM and 70 degree indoor dry bulb.
MODEL: GSH140361A* / CA*F4860C6A* +TXV / MBR1600**-1 HEATING OPERATION
Outdoor Ambient Temperature
65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 -5 -10
MBh 43.5 41.2 38.8 36.2
34.6
33.5 31.1 28.7 26.9 24.9 22.9 21.6 20.8 18.7 16.6 14.4 12.3 10.1
Delta T 37.8 35.8 33.7 31.5 30.1 29.1 27.1 25.0 23.4 21.6 19.9 18.8 18.1 16.2 14.4 12.6 10.7 8.8
KW 2.91 2.86 2.80 2.75
2.72
2.69 2.64 2.59 2.64 2.58 2.53 2.50 2.47 2.41 2.36 2.30 2.24 2.19
AMPS 13.1 12.2 11.4 10.8 10.4 10.2 9.7 9.2 8.8 8.5 8.1 7.9 7.8 7.4 7.0 6.6 6.1 5.6
COP 4.37 4.22 4.04 3.86 3.73 3.64 3.45 3.25 2.98 2.82 2.65 2.54 2.46 2.26 2.06 1.84 1.61 1.35
EER 14.9 14.4 13.8 13.2 12.7 12.4 11.8 11.1 10.2 9.6 9.1 8.7 8.4 7.7 7.0 6.3 5.5 4.6
HI PR 229 219 211 202 197 193 186 178 171 163 157 153 150 144 139 133 128 124
LO PR 83 77 72 66 63 60 55 49 44 40 35 32 31 26 23 19 17 13
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
SPLIT SYSTEM HEATING PERFORMANCE
High pressure is measured at the suction service valve ( the larger valve). AMPS = Outdoor unit amps (comp.+fan)
Low pressure is measured at the gauge port connection. KW = Total system powe
r