Goodman Mfg GPC15 SEER Air Conditioner User Manual


 
10
BLOWER PERFORMANCE DATA
Dry Coil Data
GPC15[24-48]M41A*
NOTES:
Data shown is Dry Coil. Wet Coil Pressure Drop is approximate. 0.1" H
2
O, for 2 row indoor coil; 0.2” H
2
O, for 3 row indoor coil;
and 0.3” H
2
O, for 4 row indoor coil.
Data shown does not include filter pressure drop, approx. 0.08” H
2
O.
ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON.
Reduce airflow by 2% for 208V operation.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 882 808 727 649 545 --- --- ---
WATTS 82 86 92 102 108 --- --- ---
CFM 933 873 810 733 637 584 --- ---
WATTS 93 103 109 120 126 135 --- ---
CFM 1058 1012 945 896 816 723 672 ---
WATTS 124 136 142 153 168 172 179 ---
CFM 893 824 752 665 575 --- --- ---
WATTS 87 95 101 111 115 --- --- ---
CFM 1132 1070 1011 959 889 827 733 669
WATTS 153 162 168 179 184 195 206 208
CFM 1287 1236 1165 1123 1066 1012 958 857
WATTS 211 217 228 239 244 255 265 272
CFM 852 764 711 592 545 --- --- ---
WATTS 80 82 85 95 99 --- --- ---
CFM 1232 1190 1131 1082 1023 966 889 819
WATTS 202 214 221 229 235 246 258 264
CFM 1267 1213 1162 1120 1058 1009 932 841
WATTS 218 226 236 245 247 260 272 275
CFM 1123 1070 1025 984 942 894 839 774
Watts 162 170 182 193 204 216 229 242
CFM 1437 1390 1354 1318 1281 1243 1204 1165
Watts 310 317 331 342 355 366 377 389
CFM 1528 1490 1450 1410 1383 1348 1312 1267
Watts 372 379 391 403 416 427 439 451
CFM 1199 1138 1085 1017 957 889 820 755
WATTS 162 173 185 193 211 219 232 245
CFM 1799 1745 1698 1658 1610 1560 1522 1450
WATTS 480 493 508 521 531 545 550 547
CFM 1921 1865 1818 1780 1719 1667 1579 1483
WATTS 582 585 602 625 627 621 595 569
GPC1542M41*
T1 (G) 230
T2 / T3 230
T4 / T5 230
230
230
230
GPC1548M41*
T1 (G)
T2 / T3
T4 / T5
230
Model Speed Volts
GPC1536M41*
T1 (G)
T2 / T3
T4 / T5
230
230
230
230
230
E.S.P (In. of H
2
O)
GPC1524M41*
T1 (G)
T2 / T3
T4 / T5
GPC1530M41*
T1 (G) 230
T2 / T3 230
T4 / T5 230