COOLING PERFORMANCE DATA
CKF70-5*
MODEL: CKF70-5* / A60-00-2 COOLING OPERATION
Outdoor Ambient Temperature
65°F 75°F 85°F 95°F 105°F 115°F 118°F 125°F
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 53 67 71 59 63 67 71
MBh 58.9 61.1 66.9 - 57.5 59.6 65.3 - 56.2 58.2 63.8 - 54.8 56.8 62.2 - 52.1 54.0 59.1 - 48.2 50.0 54.8 - 45.2 46.8 51.3 - 43.8 45.4 49.8 -
S/T 0.68 0.57 0.39 - 0.71 0.59 0.41 - 0.72 0.60 0.42 - 0.75 0.62 0.43 - 0.77 0.65 0.45 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.81 0.68 0.47 -
DT 20 17 13 - 20 18 13 - 20 18 13 - 20 18 13 - 20 17 13 - 19 16 12 - 18 16 12 - 18 15 12 -
1844 KW 4.65 4.75 4.90 - 5.28 5.40 5.57 - 5.81 5.94 6.13 - 6.34 6.49 6.70 - 6.83 6.99 7.22 - 7.28 7.45 7.71 - 7.68 7.85 8.13 - 7.84 8.03 8.31 -
AMPS 11.0 11.3 11.6 - 11.8 12.0 12.3 - 12.6 12.8 13.2 - 13.3 13.6 14.0 - 14.0 14.3 14.7 - 14.7 15.0 15.5 - 15.2 15.5 16.0 - 15.4 15.7 16.2 -
HI PR 168 181 191 - 189 203 215 - 215 231 244 - 245 264 278 - 276 296 313 - 304 328 346 - 323 348 367 - 331 357 377 -
LO PR 52 55 60 - 54 58 63 - 57 60 66 - 59 63 69 - 62 66 72 - 64 69 75 - 66 70 76 - 66 70 77 -
MBh 58.0 60.2 65.9 - 56.7 58.8 64.4 - 55.3 57.4 62.8 - 54.0 56.0 61.3 - 51.3 53.2 58.2 - 47.5 49.2 53.9 - 44.5 46.1 50.5 - 43.2 44.8 49.0 -
S/T 0.65 0.54 0.38 - 0.68 0.56 0.39 - 0.69 0.58 0.40 - 0.71 0.60 0.41 - 0.74 0.62 0.43 - 0.75 0.62 0.43 - 0.77 0.64 0.44 - 0.78 0.65 0.45 -
DT 21 18 14 - 21 18 14 - 21 18 14 - 21 19 14 - 21 18 14 - 20 17 13 - 19 16 13 - 19 16 12 -
70 1650 KW 4.63 4.73 4.87 - 5.25 5.37 5.54 - 5.77 5.90 6.10 - 6.31 6.45 6.66 - 6.79 6.95 7.18 - 7.24 7.40 7.66 - 7.63 7.81 8.08 - 7.80 7.98 8.26 -
AMPS 11.0 11.2 11.5 - 11.7 11.9 12.3 - 12.5 12.8 13.1 - 13.2 13.5 13.9 - 13.9 14.2 14.6 - 14.6 14.9 15.4 - 15.1 15.4 15.9 - 15.3 15.6 16.1 -
HI PR 167 180 190 - 188 202 213 - 214 230 243 - 243 262 276 - 274 294 311 - 302 325 344 - 321 345 365 - 329 354 374 -
LO PR 51 54 59 - 54 58 63 - 56 60 65 - 59 63 69 - 62 66 72 - 64 68 74 - 65 69 76 - 66 70 76 -
MBh 55.1 57.1 62.6 - 53.9 55.8 61.2 - 52.6 54.5 59.7 - 51.3 53.2 58.2 - 48.7 50.5 55.3 - 45.1 46.8 51.3 - 42.3 43.8 48.0 - 41.0 42.5 46.6 -
S/T 0.62 0.52 0.36 - 0.65 0.54 0.37 - 0.66 0.55 0.38 - 0.68 0.57 0.40 - 0.71 0.59 0.41 - 0.72 0.60 0.41 - 0.74 0.61 0.43 - 0.74 0.62 0.43 -
DT 22 19 14 - 22 19 14 - 22 19 14 - 22 19 15 - 22 19 14 - 20 18 13 - 20 17 13 - 19 17 13 -
1456 KW 4.56 4.65 4.80 - 5.17 5.28 5.45 - 5.68 5.80 5.99 - 6.20 6.34 6.55 - 6.67 6.83 7.06 - 7.11 7.28 7.53 - 7.50 7.67 7.93 - 7.66 7.84 8.11 -
AMPS 10.8 11.0 11.3 - 11.5 11.8 12.1 - 12.3 12.6 12.9 - 13.0 13.3 13.7 - 13.7 14.0 14.4 - 14.4 14.7 15.1 - 14.9 15.2 15.6 - 15.1 15.4 15.8 -
HI PR 164 176 186 - 184 198 209 - 209 225 238 - 238 256 271 - 268 289 305 - 296 319 337 - 315 339 357 - 322 347 366 -
LO PR 50 53 58 - 53 56 62 - 55 59 64 - 58 62 67 - 61 65 70 - 63 67 73 - 64 68 74 - 64 68 75 -
MBh 59.9 61.7 66.8 71.6 58.5 60.2 65.2 70.0 57.1 58.8 63.7 68.3 55.7 57.4 62.1 66.7 52.9 54.5 59.0 63.3 49.0 50.5 54.6 58.7 45.9 47.3 51.2 54.9 44.6 45.9 49.7 53.3
S/T 0.77 0.69 0.52 0.3 0.80 0.72 0.54 0.3 0.82 0.74 0.56 0.4 0.85 0.76 0.57 0.4 0.88 0.79 0.60 0.4 0.89 0.79 0.60 0.4 0.91 0.82 0.62 0.4 0.92 0.83 0.62 0.4
DT 23 21 17 12 23 22 18 12 23 22 18 12 24 22 18 12 23 21 18 12 22 20 16 11.3 21 19 16 10.9 21 19 15 10.7
1844 KW 4.69 4.79 4.94 5.1 5.33 5.44 5.62 5.8 5.86 5.99 6.18 6.4 6.40 6.54 6.76 7.0 6.89 7.05 7.29 7.5 7.35 7.52 7.77 8.0 7.74 7.92 8.20 8.5 7.91 8.10 8.38 8.7
AMPS 11.1 11.3 11.6 12.0 11.9 12.1 12.4 12.8 12.7 12.9 13.3 13.7 13.4 13.7 14.1 14.5 14.1 14.4 14.8 15.3 14.8 15.2 15.6 16.1 15.3 15.6 16.1 16.6 15.5 15.8 16.316.8
HI PR 170 183 193 201.7 191 206 217 226.4 217 234 247 257.4 247 266 281 293.2 278 300 316 329.9 308 331 349 364.5 327 351 371 387.1 335 360 380 396.7
LO PR 52 55 61 64.4 55 59 64 68.1 57 61 66 70.8 60 64 70 74.3 63 67 73 77.9 65 69 76 80.6 66 70 77 81.9 67 71 77 82.4
MBh 59.0 60.8 65.8 70.6 57.6 59.4 64.2 68.9 56.3 57.9 62.7 67.3 54.9 56.5 61.2 65.7 52.2 53.7 58.1 62.4 48.3 49.7 53.8 57.8 45.2 46.6 50.4 54.1 43.9 45.2 48.9 52.5
S/T 0.74 0.66 0.50 0.3 0.77 0.69 0.52 0.3 0.79 0.70 0.53 0.3 0.81 0.73 0.55 0.4 0.84 0.75 0.57 0.4 0.85 0.76 0.58 0.4 0.87 0.78 0.59 0.4 0.88 0.79 0.60 0.4
DT 24 22 18 13 25 23 19 13 25 23 19 13 25 23 19 13 24 23 18 13 23 21 17 11.9 22 20 17 11.5 22 20 16 11.3
75 1650 KW 4.67 4.76 4.91 5.1 5.29 5.41 5.59 5.8 5.82 5.95 6.15 6.4 6.36 6.50 6.72 7.0 6.85 7.01 7.24 7.5 7.30 7.47 7.73 8.0 7.70 7.88 8.15 8.4 7.87 8.05 8.33 8.6
AMPS 11.1 11.3 11.6 11.9 11.8 12.0 12.3 12.7 12.6 12.9 13.2 13.6 13.3 13.6 14.0 14.4 14.1 14.3 14.8 15.2 14.8 15.1 15.5 16.0 15.2 15.5 16.0 16.5 15.4 15.8 16.2 16.7
HI PR 169 182 192 200.3 190 204 216 224.8 216 232 245 255.7 246 264 279 291.2 276 297 314 327.6 305 329 347 361.9 324 349 369 384.4 332 358 378 394.0
LO PR 52 55 60 64.0 55 58 63 67.6 57 60 66 70.3 60 63 69 73.8 63 67 73 77.3 65 69 75 80.0 66 70 76 81.3 66 70 77 81.8
MBh 56.1 57.7 62.5 67.1 54.8 56.4 61.0 65.5 53.5 55.0 59.6 63.9 52.2 53.7 58.1 62.4 49.5 51.0 55.2 59.3 45.9 47.3 51.1 54.9 43.0 44.2 47.9 51.4 41.7 43.0 46.5 49.9
S/T 0.71 0.63 0.48 0.3 0.74 0.66 0.50 0.3 0.75 0.67 0.51 0.3 0.78 0.70 0.53 0.3 0.81 0.72 0.55 0.4 0.81 0.73 0.55 0.4 0.84 0.75 0.57 0.4 0.85 0.76 0.57 0.4
DT 25 23 19 13 25 23 19 13 25 23 19 13 26 24 19 13 25 23 19 13 24 22 18 12.3 23 21 17 11.8 22 21 17 11.6
1456 KW 4.59 4.69 4.83 5.0 5.21 5.32 5.49 5.7 5.73 5.85 6.04 6.2 6.25 6.39 6.61 6.8 6.73 6.89 7.12 7.4 7.18 7.34 7.59 7.9 7.56 7.74 8.01 8.3 7.73 7.91 8.18 8.5
AMPS 10.9 11.1 11.4 11.8 11.6 11.8 12.2 12.5 12.4 12.7 13.0 13.4 13.1 13.4 13.8 14.2 13.8 14.1 14.5 15.0 14.5 14.8 15.3 15.8 15.0 15.3 15.7 16.3 15.2 15.5 15.916.5
HI PR 166 178 188 196.3 186 200 211 220.3 211 227 240 250.5 241 259 274 285.4 271 291 308 321.0 299 322 340 354.7 318 342 361 376.7 326 351 370 386.1
LO PR 51 54 59 62.7 54 57 62 66.3 56 59 65 68.9 58 62 68 72.3 61 65 71 75.8 63 67 74 78.4 64 69 75 79.7 65 69 75 80.2
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves.