GE 2800 Air Conditioner User Manual


 
Installation Instructions
16
265 VOLT ELECTRICAL SUPPLY
REINSTALL JUNCTION BOX
Reinstall the junction box by engaging the left tabs
on the lower right face of the unit, aligning the
screw holes at the top and bottom and driving the
two screws until secure. Be sure that all wire leads
are inside the box and not pinched between the box
and the unit. The green insulated ground wire from
the unit MUST be connected to the branch circuit
ground wire.
Make all wire connections by using appropriate
UL-listed electrical connectors and techniques
(black to black, white to white and green to green).
4
REINSTALL JUNCTION
BOX COVER
1 Carefully tuck all wires and connections back inside
the junction box. Be sure there are no loose
connections or stray uninsulated wires exposed.
2 Place the junction box cover in place. Replace the
two screws removed earlier and tighten securely.
3 Discard the unused portion of the plug and
the cordset.
5
ATTACH CONDUIT
1 Use the round knockout at the bottom of the
junction box to attach conduit coming from the
branch circuit. Remove the knockout, attach the
conduit and bring wires into the junction box.
Leave 6of wire free at the end of the conduit
to allow connections to be made.
2 If a fuse and fuseholder are to be used, the
knockout at the top of the box is for mounting
a Buss Fuseholder. Be sure the fuse and fuseholder
are of the same rating as the branch circuit.
Leadwires at the fuse can be either soldered in
place or attached using UL-listed 1/4female
(receptacle) crimp connectors.
3
Conduit