6
Auxiliary controls on your Zoneline.
Remote Thermostat–Class 2
When this switch is enabled
(UP)
, it allows the
unit to operate off of a Class 2 Remote Control
Wall Thermostat. The unit controls are disabled.
Load Shedding (CDC)
This feature is active only if the unit is in
CDC mode. When this switch is enabled
(UP)
,
the indoor fan can be turned ON or OFF with
the unit controls.
Freeze Sentinel
When this switch is enabled
(UP)
, it turns OFF
the freeze sentinel protection feature. With the
switch disabled
(DOWN)
, the freeze sentinel is
activated which automatically provides heat
without user interface. This helps to prevent
plumbing damage by turning the heater and
indoor fan ON at 41° F and OFF at 46°F.
Constant ON Fan
When this switch is enabled
(UP)
, it allows the
indoor fan to run continuously, at high speed,
even if the unit is in the STOP position.
Occupancy Sensor
When this switch is enabled
(UP)
, it allows the
unit to utilize an infrared motion sensor and
a door switch for occupancy detection. This
feature allows an energy management system
to be installed and operated in conjunction
with the unit.
HIGH
COOL
1 2 3 4 5 6 1 2 3 4 5 67 8
UP
DOWN
UP
DOWN
Customer Service Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions
CLASS 2 (Remote Thermostat)
LOAD SHEDDING (CDC)
FREEZE Sen (Freeze Sentinel)
CONST FAN (Constant
ON Fan)
OCCUPIED
(Occupancy Sensor)