GE 2500 Air Conditioner User Manual


 
5
Auxiliary Controls on your Zoneline.
www.GEAppliances.com
Auxiliary Controls – Dip Switches
The auxiliary dip switch controls are located
behind the room cabinet, through an opening
in the control panel.
Remove the room cabinet. See the
To Remove the
Room Cabinet
section.
The factory settings will be in the
DOWN
position.
The owner is responsible for checking switches
and ensuring they are in the desired position.
HIGH
COOL
1 2 3 4 5 6 1 2 3 4 5 67 8
UP
DOWN
UP
DOWN
ALLI
2
R (All Electric Heat)
(3500 Series models only)
C: FAN CN (Cooling–Smart Fan)
H: FAN CY (Heating–Smart Fan)
CLASS 2 (Remote Thermostat)
LOAD SHEDDING (CDC)
FREEZ Sen (Freeze Sentinel)
CONST FAN (Constant ON Fan)
OCCUPIED (Occupancy Sensor)
TL1 (H) (Temp. Limit 1–Heat)
TL2 (H) (Temp. Limit 2–Heat)
TL3 (H) (Temp. Limit 3–Heat)
TL1 (C) (Temp. Limit 1–Cool)
TL2 (C) (Temp. Limit 2–Cool)
TL3 (C) (Temp. Limit 3–Cool)
Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Customer Service
All Electric Heat
This electric heat option functions only on the
3500 Series models. When this switch is enabled
(UP)
, heat pump operation is locked out, causing
the unit to provide only electric resistance heat.
Cooling–Smart Fan
When this switch is enabled
(UP)
, it allows the
indoor fan to cycle on/off with the compressor.
When this switch is disabled
(DOWN)
, it allows
the indoor fan to run continuously.
Heating–Smart Fan
When this switch is enabled
(UP)
, it allows the
indoor fan to run continuously. When this
switch is disabled
(DOWN)
, it allows the indoor
fan to cycle on/off with the heat pump or
heater operation.
ALLI
2
R (All Electric Heat)
C: FAN CN (Cooling–Smart Fan)
H: FAN CY (Heating–Smart Fan)
Dip Switches