Installation Instructions
16
ATTACH CONDUIT
1 Use the round knockout at the bottom of the
junction box to attach conduit coming from the
branch circuit. Remove the knockout, attach the
conduit and bring wires into the junction box.
Leave 6″ of wire free at the end of the conduit
to allow connections to be made.
2 If a fuse and fuseholder are to be used, the knockout
at the top of the box is for mounting a Buss
Fuseholder. Be sure the fuse and fuseholder are of the
same rating as the branch circuit. Leadwires at the
fuse can be either soldered in place or attached using
UL-listed 1/4″ female (receptacle) crimp connectors.
3
Conduit
REINSTALL JUNCTION BOX
• Reinstall the junction box by engaging the left tabs
on the lower right face of the unit, aligning the
screw holes at the top and bottom and driving the
two screws until secure. Be sure that all wire leads
are inside the box and not pinched between the box
and the unit.
The identified (ribbed) Neutral wire of the cordset
MUST be connected to the white Neutral wire of
the branch circuit. The green insulated ground wire
from the unit MUST be connected to the branch
circuit ground wire.
4
265 VOLT ELECTRICAL SUPPLY
MAKE WIRING CONNECTIONS
1 Make all wire connections by using appropriate
UL-listed electrical connectors and techniques
(black to black, white to white and green to green).
2 Carefully tuck all wires and connections back inside
the junction box. Be sure there are no loose
connections or stray uninsulated wires exposed.
3 Place the junction box cover in place. Replace the
two screws removed earlier and tighten securely.
4 Discard the unused portion of the plug and
the cordset.
5
NOTE: Order Kit RAK4002CW to enable a quick
disconnect inside the junction box.