Friedrich SH20 Air Conditioner User Manual


 
Page 7
INSTALLATION INSTRUCTIONS
Models SH14 and SH20
NOTE: THIS MANUAL INCLUDES INSTALLATION INSTRUCTIONS FOR BOTH WINDOW MOUNT AND THROUGH-
THE-WALL INSTALLATIONS
Model Number Plug Type Circuit Rating
Time Delay Fuse
SH14 Junction Box 250V-15 Amp
SH20 Junction Box 250V-15 Amp
SECTION I: ELECTRICAL REQUIREMENTS
ALL FIELD WIRING MUST MEET THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70)
ARTICLE 501.
THE FIELD-PROVIDED CIRCUIT PROTECTION DEVICE (HACR CIRCUIT BREAKER OR TIME DELAY FUSE) MUST
NOT EXCEED THE AMPACITY INDICATED ON THE PRODUCT NAMEPLATE.
IMPORTANT: Before you begin the actual installation of your air conditioner, check local electrical codes and the
information below.
Your air conditioner must be connected to a power supply with the same A.C. voltage and frequency (hertz) as marked on
the data plate located on the chassis. Only alternating current (A.C.), no direct current (D.C.), can be used.
An overloaded circuit will invariably cause malfunction or failure of the air conditioner; therefore, it is extremely important
that the electrical power is adequate. Consult your dealer or power company if in doubt.
The following instructions are for HAZARDGARD models and cabinet sizes listed below.
GROUPS CABINET SIZE (H x W x D)
SMALL CHASSIS SH14 15–15/16" x 25–15/16" x 27–3/8"
(405 mm x 660 mm x 695 mm)
MEDIUM CHASSIS SH20 17–15/16" x 25–15/16" x 27–3/8"
(455 mm x 660 mm x 695 mm)