Friedrich R410A Air Conditioner User Manual


 
Wire Size
ELECTRICAL REQUIREMENTS
Unit MUST
Supply voltage
For VPAK Cool with Electric Heat 9-18K
ELECTRIC SHOCK HAZARD
WARNING
Turn off electric power before service or instal-
lation. All electrical connnections and wiring
MUST be installed by a qualified electrician and
conform to the National Electrical Code and all
local codes which have jurisdiction. Failure to
do so can result in personal injury and/or death.
NOTICE
Not following the previous WARNING could result
in fire or electrically unsafe conditions which could
cause moderate or serious property damage.
Read, understand and follow the previous warning.
Supply voltage to the unit should be a nominal 208/230 volts. It must be between 197 volts and 253 volts. Supply voltage to
the unit should be checked WITH THE UNIT IN OPERATION. Voltage readings outside the specified range can be expected
to cause operating problems. Their cause MUST be investigated and corrected.
“Use ONLY time delayed fused disconnect or HACR type circuit breaker as indicated on the unit’s rating plate. Proper
current protection to the unit is the responsibility of the owner”.
Heater Watts 2500/2050 3400/2780 5000/4090 2500/2050 3400/2780 5000/4090 2500/2050 3400/2780 5000/4090
Voltage
Heating BTU/h 8500/7000 11600/9500 17000/13900 8500/7000 11600/9500 17000/13900 8500/7000 11600/9500 17000/13900
Heating Current (Amps) 10.9/9.9 14.8/13.4 21.7/19.7 10.9/9.9 14.8/13.4 21.7/19.7 10.9/9.9 14.8/13.4 21.7/19.7
Minimum Circuit Ampacity
15 19.9 28.6 15 19.9 28.6 15 19.9 28.6
Branch Circuit Fuse (Amps) 15 20 30 15 20 30 15 20 30
LRA - Compressor (Amps) 22 22 22 30 30 30 42 42 42
Cooling Current (Amps) 4.2/4.4 4.2/4.4 4.2/4.4 5.2/5.4 5.2/5.4 5.2/5.4 8 1/8.. 6 8 1/8.. 6 8 1/8.. 6
Basic heater Size 2.5 Kw 3.4 Kw 5.0 Kw 2.5 Kw 3.4 Kw 5.0 Kw 2.5 Kw 3.4 Kw 5.0 Kw
Power Connection
230/208 230/208 230/208
VEA09K VEA12K VEA18K
HARD WIRED HARD WIRED HARD WIRED
Electrical Data
Recommended Branch
Circuit Wire Sizes **
* AWG-American Wire Gauge
14 12 10 14 12 10 14 12 10
For VPAK Heat Pumps 9-18K
All 208/230v chassis must be hard wired with properly sized breaker. See nameplate for specific chassis electrical
requirements. See below for unit wiring. For wall thermostat wiring, see page 12.
Use HACR type breakers to avoid
nuisance trips. All field wiring must be done in accordance with NEC and local codes.
Heater Watts 2500/2050 3400/2780 5000/4090 2500/2050 3400/2780 5000/4090 2500/2050 3400/2780 5000/4090
Voltage
Heating BTU/h 8500/7000 11600/9500 17000/13900 8500/7000 11600/9500 17000/13900 8500/7000 11600/9500 17000/13900
Heating Current (Amps) 10.9/9.9 14.8/13.4 21.7/19.7 10.9/9.9 14.8/13.4 21.7/19.7 10.9/9.9 14.8/13.4 21.7/19.7
Minimum Circuit Ampacity 15 19.9 28.6 15 19.9 28.6 15 19.9 28.6
Branch Circuit Fuse (Amps) 15 20 30 15 20 30 15 20 3
0
LRA - Compressor (Amps) 18.5 18.5 18.5 26 26 26 42 42 42
Cooling Current (Amps) 4.1/4.3 4.1/4.3 4.1/4.3 5.3/5.5 5.3/5.5 5.3/5.5 8.2/8.6 8.2/8.6 8.2/8.6
Basic heater Size 2.5 Kw 3.4 Kw 5.0 Kw 2.5 Kw 3.4 Kw 5.0 Kw 2.5 Kw 3.4 Kw 5.0 Kw
Power Connection
032/802802/032802/032
DERIW DRAHDERIW DRAHDERIW DRAH
VHA09K
VHA12K
VHA18K
Electrical Data
Recommended Branch
Circuit Wire Sizes
* AWG-American Wire Gauge
0141012141 01214121