Emerson Process Management XFC Carbon Monoxide Alarm User Manual


 
Product Data Document
1660DS-7c
July 17, 2007 - Page 8
Bristol
®
ControlWave
®
XFC
Remote Automation Solutions
Website: www.EmersonProcess.com/Remote
RTD probe interchangeability can add ±0.7°C of
uncertainty to the measurement).
RTD Conversion Accuracy: ± 0.1°C, or ± 0.1%
of reading, whichever is greater
Ambient temperature effect on RTD
measurement: ±0.01°C / ºC max
Long Term Stability at Constant Conditions:
±0.25ºC / month max
Accessories
Bendable RTD
The user can choose a bendable RTD that is at-
tached to the ControlWave XFC via an armored
cable of 6-foot, 15-foot or 25-foot length. The
individual wires attach to a terminal block on the
termination plate.
The RTD assembly includes a tting, which is
installed in the right-hand (when looking at the ter-
mination plate end of the instrument) conduit port.
Normally, this RTD would be used to provide the
process temperature input but the standard ap-
plication program also allows the user to select an
external temperature transmitter, instead.
The bendable RTD is a “one size ts all” solution
that is perfect for most applications and excellent for
depot-level inventory situations in which the ultimate
installation (and, therefore, thermowell depth) is not
necessarily known.
The 12” probe can quickly be inserted in a
thermowell, whereupon the user can tighten the in-
cluded tting to lock it in place and bend the excess
length out of the way.
Note that a thermowell is required for this bendable
RTD!
Note also that the bendable RTD assembly is ap-
proved only for use in Class I, Division 2 hazardous
areas and is not explosion proof.
Bendable RTD Assembly Part Numbers
6 Foot Cable - 621564-01-0-KIT
15 Foot Cable - 621564-02-8-KIT
25 Foot Cable - 621564-03-6-KIT
PC CABLES
PC cables for ControlWave XFC will be released in
the near future
STANDARD APPLICATION PROGRAM AND PC
MENU PAGES
ControlWave XFC normally comes pre-loaded
with the Standard Application Program (.pro le)
in Flash. However, the PC menu pages are not
loaded in Flash but are available either via the Em-
erson Process Management web site or on a CD.
The CD is the “BSI Cong” CD, which also contains
the LocalView Calibration Tool as well as a copy of
the Standard Application Program.
BSI Cong CD – p/n 395575-02-8
For users wishing to modify the Standard Applica-
tion Program, it is available as source code. Please
contact Emerson’s Remote Automation Solutions
Application Services department for information.