Emerson Process Management XFC Carbon Monoxide Alarm User Manual


 
Product Data Document
1660DS-7c
July 17, 2007 - Page 3
Bristol
®
ControlWave
®
XFC
Remote Automation Solutions
Website: www.EmersonProcess.com/Remote
ESD: Field connected circuits meet the
requirements of IEC 1000-4-2 for ESD
withstand capability up to 4KV.
Nema Rating: Nema 4, 4x and 7.
Hazardous Area Approvals
Explosion-proof for operation in Class I, Division
1 Hazardous Areas: UL/CUL Approved.
Non-incendive for Class I, Division 2 Hazardous
areas: UL/CUL Approved.
Selection Item Descriptions and
Specications
Emerson’s Bristol Sensor Assembly
The sensor assembly is Selection “ABC” in the
model specication, e.g. “022” for the 100 psi gauge
pressure sensor or "142" for a 300" DP/2000 psig
static pressure multivariable sensor assembly.
Using the integral sensor assembly is the easiest
implementation for a single meter run; however, the
standard application program also allows use of
external transmitters.
Multiple-run systems can use the integral sensor
assembly for the rst run and an external, smart
multivariable transmitter, such as the Bristol 3808
MVT from Emerson(which includes the exact same
sensor assembly), for additional meter runs.
If the sensor assembly requires a repair, the user
Bristol DP/P Multivariable
Sensor Assembly
can change it out and continue operating with the
"top end" electronics, including ow information,
alarms and historical archives, all intact.
Emerson recommends that users practice “depot
level” service, in other words, that the sensor as-
sembly be removed and replaced at the user’s shop
rather than out at the site.
Each sensor assembly has a nine-digit part number,
which can be used to specify a replacement part
(please refer to the last page of this product data).
Physical Specications – MVT Assembly
Flange Material: Hastelloy C or 316 Stainless
Steel
Flange Bolt Material: Hastelloy C or 316
Stainless Steel
Diaphragm Material: Hastelloy C or 316
Stainless Steel
Fill Medium: DC 200 Silicone
Flange Process Connections: ¼” NPT
Connects to the main electronics via a
dedicated SPI bus cable.
Note: Wetted parts materials, Hastelloy C or Stain-
less Steel, are specied in Selection “D.”
Accuracy and Performance Specications
– Gauge Pressure or Differential Pressure/
Static Pressure
Combined effects of nonlinearity,
nonrepeatability and hysteresis at reference
pressure and over the operating temperature
range: GP, DP and SP linear mode: ±0.075% of
Calibrated Span or 0.015% of URL, whichever
is greater.
Temperature effect on Static and Differential
pressure: ±0.21%URL maximum combined shift
of zero and span with an ambient temperature
change of 60ºC (108ºF)
Static Pressure Effects On Differential Pressure:
Zero error: ±0.1% URL, for a change in static
pressure of 1000 psi; Span error: ±0.1%