Emerson Process Management XFC Carbon Monoxide Alarm User Manual


 
Product Data Document
1660DS-7c
July 17, 2007 - Page 2
Bristol
®
ControlWave
®
XFC
Remote Automation Solutions
Website: www.EmersonProcess.com/Remote
Application Areas
ControlWave XFC is appropriate to all applications
for ow computers, including those that require
process control or extension to two meter runs, for
example:
Production wells
Injection wells
Production optimization applications
Off-shore platforms
Separation plants
Compressor stations
Storage facilities
Transmission metering stations
Distribution/LDC metering/gate stations
Using the gauge pressure sensor, ControlWave
XFC provides accurate, P/T measurement for linear
meters, including positive displacement, turbine
and ultrasonic technologies. The multivariable,
DP/P sensor applies best to orice metering, where
accurate, three-variable (DP/P/T) measurement is
required.
Package Description
ControlWave XFC is ordered using a model number
specication. The complete model number speci-
cation is included toward the end of this product
data.
Standard equipment includes an explosion-proof
housing, two-board electronics assembly with 3 se-
rial ports RTD interface, 2-line LCD, and the stan-
dard API 21.1 EFM application program. Emerson’s
Bristol smart sensor assembly, which provides
measurement of gauge pressure or differential pres-
sure plus static pressure, is also standard equip-
ment.
The model number additionally allows a user to
specify the following:
Sensor upper range limits
Wetted parts material, stainless steel or
Hastelloy C
Optional manifold adapters
Optional mounting bracket
Standard application program
I/O conguration choices are no I/O; 2 DI, 2
HSC, 4 DO; and 2 DI, 2 HSC, 4 DO plus 3 AI
and 1 AO.
Specications – Package
Dimensions: Please see the diagram on page
14
Clearance: Please allow at least 2.5” space on
either side for cabling.
Dimensions: MVT Wet End: 3” H x 3¾” W x 2½”
D
Weight: 12 lbs.
Mounting: Pipe-mounting or direct-mounting is
recommended; a 2” pipe-mount kit is optional.
Specications – Operating Environment
Wide operating power input voltage range of
6.0 to 30.0 Vdc. Shutdown sequence occurs at
5.46 Vdc nominal.
Power input surge suppression: 30V transorb
to ground meets ANSI/IEEE C37.90-1978.
Fuse: 0.375 A slow blow.
Operating Temperature Range: -40 to 176ºF
(-40 to 80ºC).
Operating Humidity Range: 10 to 95% RH non-
condensing.
Vibration Rating: Maintains proper operation
while subjected to a 2.0g acceleration over 10-
150 Hz and 1.0g acceleration over 150-2000
Hz.
RFI Immunity: In conformity with IEC 1000-4-3
Level 2 80 MHz to 1000 MHz.