Emerson CF955ORB 00 Fan User Manual


 
NOTE: Take care not to scratch fan housing when
installing blades.
9. Remove two of the four screws in the motor
assembly and loosen the remaining two screws
(Figure 6).
10.Connect the terminals of the lower housing
assembly to the terminals of the fan motor
assembly (Figure 6).
11.Attach the lower housing assembly to the fan motor
using the two key slot holes. (Figure 7). Secure the
lower housing assembly by tightening the two
screws. Reinstall the two screws that were removed.
NOTE: Make sure wires and terminals are positioned
in raised center area of lower housing assembly,
and not pinched between fan and light kit.
5
Electrical Requirements
If your fan is to replace an existing ceiling light fixture,
turn electricity off at the main fuse box at this time and
remove the existing light fixture.
Your new ceiling fan will require a grounded electrical
supply line of 120 volts AC, 60 Hz, 15 amp circuit.
The outlet box must be securely anchored and
capable of withstanding a load of at least 50 pounds.
TERMINALS
LOWER
HOUSING
ASSEMBLY
FAN MOTOR
ASSEMBLY
REMOVE
2 SCREWS
LOOSEN
2 SCREWS
FUSE AND
FUSE HOLDER
Figure 6
LOWER
HOUSING
ASSEMBLY
RAISED CENTER
AREA OF LIGHT
KIT HOUSING
SCREWS (2)
KEY
SLOT
HOLE (2)
Figure 7
To reduce the risk of fire, electric shock, or personal
injury, mount fan to outlet box marked “Acceptable
for Fan Support”, and use screws supplied with
outlet box. Most outlet boxes commonly used for
support of light fixtures are not acceptable for fan
support and may need to be replaced. Consult a
qualified electrician if in doubt.
WARNING
!
Turning off wall switch is not sufficient. To avoid
possible electrical shock, be sure electricity is
turned off at the main fuse box before wiring. All
wiring must be in accordance with National and
Local codes and the ceiling fan must be properly
grounded as a precaution against possible electrical
shock.
WARNING
!
To avoid fire or shock, follow all wiring instructions
carefully.
Any electrical work not described in these
instructions should be done or approved by a
licensed electrician.
WARNING
!
How to Hang Your
Ceiling Fan
CEILING
FLOOR
AT LEAST
7'
Figure 8
The fan must be hung with at least 7' of clearance
from floor to blades (Figure 8).
WARNING
!
The outlet box and joist must be securely mounted
and capable of supporting at least 50 lbs. Use only a
U.L. outlet box listed as “Acceptable for Fan
Support”.
WARNING
!
8. To ensure proper blade assembly, make sure the
label on the blades are facing the bottom of the
ceiling fan. Slide blade through center slot in fan
housing. Mount blade to fan housing using three
3/16-24 x 1/2” slotted Phillips washer head blade
screws (Figure 5).
MOTOR
HUB
3/16-24 x 1/2" SLOTTED
PHILLIPS WASHER HEAD
BLADE SCREWS
FAN BLADE
BLADE SLOT
IN HOUSING
LABEL
(LOCATED ON
BOTTOM OF BLADE)
Figure 5
U.L. Model No.: CF955