Emerson 3000 Air Conditioner User Manual


 
Installation (Applicable to all Models)
7Liebert
®
Challenger 3000
2.4.1 Handling With Skid
Always keep the unit upright, indoors and protected from damage.
If possible, transport the unit using a fork lift; otherwise, use a crane with belts or cables,
avoiding pressing on the top edges of the packaging.
If using a fork lift, make sure the forks, if adjustable, are spread to the widest allowable distance
to still fit under the skid.
NOTICE
Risk of overhead interference. Can cause unit and/or structure damage.
Refer to the installation plans prior to moving the unit to verify clearances.
While on the skid, the unit is too tall to fit through a standard height doorway (83 in. or
2108mm tall). Any attempt to move the unit, while on the skid, through a standard doorway
will cause damage to the unit.
2.4.2 Removal of Skid
Remove the plywood skirting that keeps the skid and unit in place.
Raise the Liebert Challenger 3000 off the skid. Emerson recommends using a fork lift (see
Figure 1) or similar machine to ensure that the unit is lifted properly.
Once the unit is raised, the skid can be removed.
Figure 1 Removing the Liebert Challenger 3000 from skid
Table 1 Unit net weight
Model Lb. (kg)
036E/035E 535 (243)
060E/059E 545 (247)
042A/040A 615 (279)
067A/065A 670 (304)
046WG/045WG 700 (318)
071WG/070WG 750 (340)
061G/058G 785 (356)
068C/072C 545 (247)
102C/101C 555 (252)
Remove plywood skirting holding
unit and skid in place.
Raise unit with forklift
or similar machine.