Emerson 1F97-1277 Thermostat User Manual


 
5
To enter the menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Cong touch key. This displays
menu item #1 in the table below. Press
to advance to the next menu item or to return to a previous menu item. Press
or
to change a menu item.
Installer Note: To default the programming, clock and Conguration Menu to the Factory Default Settings, press the
,
and SYSTEM keys simultaneously. The thermostat display will go blank for a few seconds, and then all segments will display
momentarily. For heat pump systems, Conguration Menu item 1 must be set to match the heat pump system.
If rst item does not show SS1 or HP1, you have an earlier thermostat model and need Instruction Sheet 37-6814D.
CONFIGURATION MENU
Menu
Reference
Number
Program-
mable
Non-
Program-
mable
Press
Button
Displayed
(Factory
Default)
Press
or to
select from listed
options Comments
1 1 1 SS1 HP1, SS1 Selects Single Stage or Heat Pump
(1 compressor)
2 2 2
(ELE) GAS GAS setting: furnace controls blower
ELE setting: thermostat controls blower
3 3 3
Days, (7) P 5+1+1 or 0 Programs per week. (0 = non-programmable)
4 4 NA
PS (4) 2 Program periods per day
4 = Morning, Day, Evening, Night
2 = Day, Night
5 5 4
Cool-Off-
Heat-Auto
Cool-Off-Heat,
Off-Heat, Cool-Off
System switch conguration in single stage
Cool-Off-Heat-
Emer-Auto
Cool-Off-Heat-Emer,
Off-Heat-Emer,
Cool-Off
System switch conguration, heat pump mode
6 6 NA
E (On) OFF Selects Energy Management Recovery, E (with programming option on)
7 7 5
Cr, Heat (FA) SL Selects Adjustable Anticipation, cycle rate, Heat
8 8 6
Cr, Cool (FA) SL Selects Adjustable Anticipation, cycle rate, Cool
9 9 7
Cr/AU, Emer (FA) SL Selects Adjustable Anticipation, cycle rate auxiliary, (This item is
only to appear if HP1 is selected above)
10 10 8
CL (OFF) On Selects Compressor Lockout
11 11 9
dL (On) OFF Selects Continuous Display backlight & intensity
12 12 10
dL (LO) HI Selects Backlight Intensity
13 13 11
0 4, LO to 4, HI Selects Adjustable Ambient Temperature Display [range -4 (LO)
to +4 (HI)]
14 14 12
°F °C Selects °F/°C Display (temperature units in Fahrenheit or Celsius).
15 15 13
b (On) OFF Selects audible Beeper On/Off
16 16 14
dS (On) OFF Selects Daylight Saving Time calculation
17 17 15
AS, Heat (On) OFF Selects Automatic Schedule for comfort temperature Programming,
heat mode
18 18 16
AS, Cool (On) OFF Selects Automatic Schedule for comfort temperature Programming,
cool mode
19 19 17
CS, (OFF)
Cool Savings
1-2-3-4-5-6 Selects Cool Saving Feature & amount
20 20 18
HL, Heat (99) 62-98 TEMPERATURE LIMIT, HEAT (max. heat set point)
21 21 19
LL, Cool (45) 46-82 TEMPERATURE LIMIT, COOL (min. cool set point)
22 22 20
OFF,
Keypad Lockout
L (total), P (partial),
Temperature Limit
(limited temperature
range)
Selects Keypad Lockout
000 001-999 Selects Keypad Lockout Combination (active only if keypad Lockout
is selected).
23 23 21
FS, Heat (On) OFF Fast second stage of heat (not available if SS1 is selected above)
24 24 22
Remote (OFF) On Remote temperature sensor, enable/disable
In, Remote Outdoor Remote Remote temperature sensor (Indoor/Outdoor)
LS (On) OFF Local temp. Sensor enable/disable (only when Indoor Remote is
selected On).
25 25 23
dF (5) 5-50 Selects Dual Fuel Feature & set point (in Fahrenheit)
(applicable only when HP1 is selected)
Cd (60) 0-99 Selects Compressor delay in seconds (only when dF is selected >5)
26 26 24
Change Filter
(OFF)
On Selects Change lter feature
200 Hours 25-1975
(in increments
of 25 hours)
Change lter, duration hours
INSTALLER/CONFIGURATION MENU