Desa HRB3930/3924 Electric Heater User Manual


 
www.desatech.com
119426-01A 15
Pipe Cap Tee
Nipple Joint
INSTALLATION
Continued
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up. NPT
tap must be upstream from heater (see Figures 15
or 16, depending on your model).
IMPORTANT: Install equipment shutoff valve
in an accessible location. The equipment shutoff
valve is for turning on or shutting off the gas to
the appliance.
Check your building codes for any special re-
quirements for locating equipment shutoff valve
to replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could result
in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment trap in
supply line as shown in Figures 15 or 16, depend-
ing on your model. Locate sediment trap where it is
within reach for cleaning. Install in piping system
between fuel supply and heater. Locate sediment
trap where trapped matter is not likely to freeze.
A sediment trap traps moisture and contaminants.
This keeps them from going into heater controls. If
sediment trap is not installed or is installed wrong,
heater may not run properly.
CAUTION: Avoid damage to
regulator. Hold gas regulator
with wrench when connecting
it to gas piping and/or ttings
(Thermostatically-Controlled
Models Only).
CAUTION: Avoid damage to
gas control. Hold gas control
with wrench when connecting
it to gas piping and/or ttings
(Remote-Ready Models Only).
Figure 15 - Gas Connection
(Thermostatically-Controlled Models Only)
* Purchase the optional CSA design-certied
equipment shutoff valve from your dealer. See
Accessories, page 42.
**Minimum inlet pressure for purpose of input
adjustment.
Figure 16 - Gas Connection (Remote-
Ready Models Only)
Gas
Control
Tee Cap Pipe
Joint Nipple
3" Minimum
Gas
Regulator
PROPANE/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
CSA Design-Certied
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved Flexible
Gas Hose (if
allowed by local
codes)
Sediment Trap
NATURAL
From Gas
Meter
(5" W.C.**
to 10.5"
W.C.
Pressure)
3" Minimum
Sediment Trap
CSA Design-Certied
Equipment Shutoff Valve
With 1/8" NPT Tap*
Approved Flexible
Gas Hose (if
allowed by local
codes)
PROPANE/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)
NATURAL
From Gas
Meter
(5" W.C.**
to 10.5"
W.C.
Pressure)