INSTALLATION
Continued
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open.
If running heater with damper
open, noncombustible material
above replace opening is not
needed. Go to Installing Damper
Clamp Accessory for Vented
Operation, page 12.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using Mantel.
If not using a mantel, follow the information on
this page.
You must have noncombustible material(s) above
the replace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2" thick. With sheet metal, you must have non-
combustible material behind it. Noncombustible
material must extend at least 8" up (for all models).
If noncombustible material is less than 12", you
must install the replace hood accessory (24" and
30" Models Only). See Figure 5 for minimum
clearances.
If Using Mantel
You must have noncombustible material(s) above
the replace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2" thick. With sheet metal, you must have non-
combustible material behind it. Noncombustible
material must extend at least 8" up (for all models).
If noncombustible material is less than 12", you
must install the replace hood accessory (24"
and 30" Models Only). Even if noncombustible
material is more than 12", you may need the hood
accessory to deect heat away from your mantel
shelf. See Figure 5 and Figures 6 and 7, page 9,
for minimum clearances.
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
ue damper open. Go to Installing Damper Clamp
Accessory for Vented Operation, page 12.
Heat Resistant
Material
(A)
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
Noncombustible
Material Requirements for
Distance (A) Safe Installation
1
2" or more Noncombustible mate-
rial OK.
Between 8" and 12"
24" or 30" Models:
Install fireplace hood
accessory (GA6050,
GA6052 or GA6053 see
Accessories, page 42).
18" Model: Noncombus-
tible material OK.
Less than 8"
Noncombustible mate-
rial must be extended to
at least 8". See Between
8" and 12", above. If you
cannot extend material,
you must operate heater
with ue damper open.
MANTEL CLEARANCES
In addition to meeting noncombustible material
clearances, you must also meet required clearances
between replace opening and mantel shelf. If
you do not meet the clearances listed below, you
will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel
shelf and top of replace opening, a hood is not
required (see Figure 6, page 11).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 11, are
not met, you must have a hood. When using a hood
there are still certain minimum mantel clearances
required. Follow minimum clearances shown in
Figure 7, page 11, when using hood.