Desa FB36NCA, FB42NC, FB36CA, FB42C Indoor Fireplace User Manual


 
5
103451
OWNER’S MANUAL
DETERMINING AIR FLOW FOR FIREBOX LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install firebox plus any adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height = ________cu. ft. (volume of space)
Example:
Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
_____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)
Example:
3168 cu. ft. (volume of space) ÷ 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free firebox ____________ Btu/Hr
Gas water heater* ____________ Btu/Hr
Gas furnace ____________ Btu/Hr
Vented gas heater ____________ Btu/Hr
Gas firebox logs ____________ Btu/Hr
Other gas appliances* +____________ Btu/Hr
Total =____________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
______________ Btu/Hr (maximum the space can support)
______________ Btu/Hr (actual amount of Btu/Hr used)
Example:
63,300 Btu/Hr (maximum the space can support)
79,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:
A. Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air from Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 6.
C. Install a lower Btu/Hr firebox, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.
AIR FOR
COMBUSTION AND
VENTILATION
Continued
Continued
WARNING: If the area in which the firebox and gas log heater may be operated is smaller than that defined as
an unconfined space, provide adequate combustion and ventillation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3
or applicable local codes.
Example:
Gas water heater 40,000 Btu/Hr
Vent-free firebox
with log heater + 39,000 Btu/Hr
Total = 79,000 Btu/Hr