VENTING INSTALLATION INSTRUCTIONS
Continued
Horizontal (H
1
Horizontal (H
1
Horizontal (H
2
5' min. 2' max. 6' max.
6' min. 4' max. 12' max.
7' min. 6' max. 18' max.
8' min. 8' max. 20' max.
20' max. 8' max. 20' max.
Figure 17 - Horizontal Termination Conguration for Venting Using Two 90° Elbows
45° Elbow
HORIZONTAL SYSTEM INSTALLATION
The following congurations show the minimum
vertical rise requirements for a horizontal system
using two 90° elbows.
Horizontal (H
1
Horizontal (H
2
5' min. 6' max.
6' min. 12' max.
7' min. 18' max.
8' min. 20' max.
20' max. 20' max.
Figure 18 - Horizontal Termination Conguration for Venting Using Two 90° Elbows
with Termination at 90° with Fireplace
45° Elbow