All installations and services must be performed by qualified service personnel.
5
Heat Mode
When a call for heat ("W") is received from the thermostat, if the “Cool” mode is not already active, the “T-T”
terminal is energized and the blower on delay is started. The on-off pattern of DIP switch SW2 (positions 1
and 2) select one of four blower on delay values (see Table 1). When the delay time has elapsed, a speed value
is read from DIP switch SW1 positions 1 through 3 (see the CFM Tables) and the blower is ramped up to that
speed.
The control remains in steady heat mode until the thermostat is satisfied. When the call for heat signal is
removed, the “T-T” terminal is de-energized and the blower off delay is started. The on-off pattern of DIP
switch SW2 (positions 3 and 4) select one of four blower off delay values (see Table 1). When the delay time
has elapsed, the blower is ramped toward zero.
Table 1: ON and OFF Blower Delay Time Switch Settings
Motor Blower Speed
Three blower speed outputs are provided. A “G” call for fan will provide the Low speed only. A “W”
heat call will provide the Heat speed only. A “Y” cooling call will provide the Cool speed only.
In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by the
input that was first initiated. In the case where the control is in a cooling mode with both “Y” and “W”
inputs energized and then the “Y” input is removed, the cooling blower off time will be executed prior to
the control switching into a heating mode. In the case where the control is in a heating mode with both
“Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time will be
executed prior to the control switching into a cooling mode. In the case where a call for fan “G” already
exists and either a “W” or a “Y” call is initiated, the blower speed will switch to the respective “W” or a
“Y” speed following the blower on delay for that call.
Six dip switches select Speed values for heat, cool, fan and dehumidification blower speeds (see the CFM
Tables).
Blower On and Off Delays
Four Heat blower on and four blower off delays are selected by two dip switches for each function. Refer
to Table 1 for specific delay values.
Speed Selection values
Three dip switches select 8 cooling speeds. Dependant fan, and dehumidification speeds are selected by
the same switches, their tabular values are enacted when their function is called.
Three additional dip switches select 8 heating speeds which are enacted when heat is called. This allows
independent selection of heating and cooling capacity parameters. See the CFM Tables for speeds.
DIP SWITCH 2 SECTION
STATE
BLOWER DELAY
TIMES
2 1 4 3 ON - SEC OFF - MIN
OFF OFF 30
OFF ON 60 Factory Set
ON OFF 120
ON ON 240
OFF OFF 2
OFF ON 4 Factory Set
ON OFF 6
ON ON 8