Crestron electronic CHV-TSTAT Thermostat User Manual


 
Crestron CHV-TSTAT and CHV-THSTAT Thermostats
2. System Performance
Press the MODE button to access the next menu, SYSTEM PERFORMANCE. Press
VIEW to select preferences. Press the Arrow keys (▲▼) to select the value of the
parameter.
MODE
VIEW
T
T
CRESTRON
SETUP: SYSTEM PERF
Heat Anticipator:
Cool Anticipator:
Auto Mode DdBand:
HP Balance Pt:
AUX Balance Pt:
3
3
2
0
0
0
15
0
Anticipators
(valid selections are 1 through 6)
Low number = more frequent cycles and faster
response (tighter regulation)
High number = less frequent cycles and slower
response (looser regulation)
Auto Mode Dead Band
(valid selections are 2 through 6
0
)
The minimum differential between heating
and cooling setpoints (Dual Setpoint Auto
set to Yes in Display Options on page 19).
HP Balance Point (Heat Pump Systems only)
Minimum outdoor temperature at which the heat
pump will run (requires outdoor sensor)
AUX Balance Point (Heat Pump with Aux only)
Maximum outdoor temperature at which Aux Heat
System supplements the heat pump (requires
outdoor sensor)
NOTE: Setting the HP Balance Point to 0º can disable Heat pump. Setting the Aux
Balance Point to 90º can disable Aux Heat.
3. Humidifier/Fan Options
Press the MODE button to access the HUMIDIFIER/FAN OPTIONS. Press VIEW
to select option. Press the Arrow keys (▲▼) to select the value of the parameter.
MODE
VIEW
T
T
CRESTRON
SETUP: HUM/FAN OPTS
Disp Humidity Pgs?
Cold Weather Comp?
Run Fan in Ht Calls?
Y
Y
N
Display Humidity Pages?
Cold Weather Compensation?
Run Fan in Heat Calls?
Yes or No
Yes or No. Modifies the humidifier output
to prevent condensation on the windows.
Requires an outdoor temperature sensor.
Yes or No
Most heating systems run the fan
automatically. If your heating system
requires fan control, select Yes.
Operations and Installation Guide – DOC. 8163A Thermostats: CHV-TSTAT and CHV-THSTAT 17